2 Instructions

2-262

CP1E CPU Unit Instructions Reference Manual(W483)

Note 1 When the unit is designated as 1, the range is from 1 to 8,191 times the period. When the unit is designated as 9, the

range is from 0.1 to 819.1 s. When 9 is designated, set the integral and derivative times to within a range of 1 to 8,191
times the sampling period.

2 Setting the 2-PID parameter (

α) to 000 yields 0.65, the normal value.

3 When the manipulated variable output limit control is enabled (i.e., set to “1”), set the values as follows:

0000

≤ MV output lower limit ≤ MV output upper limit ≤ Max. value of output range

Bit 00 of C+5

PID forward/reverse
designation

Determines the direction of the proportional
action.

0:

Reverse action

1:

Forward action

Not allowed

Bit 12 of C+6

Manipulated variable
output limit control

Determines whether or not limit control will apply
to the manipulated variable output.

0:

Disabled (no limit control)

1:

Enabled (limit control)

Bits 08 to 11
of C+6

Input range

The number of input data bits.

0: 8 bits

5: 13 bits

1: 9 bits

6: 14 bits

2: 10 bits

7: 15 bits

3: 11 bits

8: 16 bits

4: 12 bits

Bits 04 to 07
of C+6

Integral and deriva-
tive unit

Determines the unit for expressing the integral
and derivative constants.

1:

Sampling period multiple

9:

Time (unit: 100 ms)

Bits 00 to 03
of C+6

Output range

The number of output data bits. (The number of
output bits is automatically the same as the num-
ber of input bits.)

0: 8 bits

5: 13 bits

1: 9 bits

6: 14 bits

2: 10 bits

7: 15 bits

3: 11 bits

8: 16 bits

4: 12 bits

C+7

Manipulated variable
output lower limit

The lower limit for when the manipulated variable
output limit is enabled.

0000 to FFFF (binary)
(See note 3.)

C+8

Manipulated variable
output upper limit

The upper limit for when the manipulated variable
output limit is enabled.

0000 to FFFF (binary)
(See note 3.)

Bit 15 of C+9

AT Command Bit

This control bit starts autotuning.

• Set the AT Command Bit to 1 to perform auto-

tuning. (Autotuning can be started while
PIDAT(191) is being executed.)

• This bit is turned OFF automatically when auto-

tuning is completed.

Autotuning will be interrupted if the AT Command
Bit is turned OFF manually. In this case, the PID
constants will be enabled if they were already cal-
culated when autotuning was interrupted.

As a Control Bit:

• 0

→

1:

Executes autotuning.

• 1

→

0:

Interrupts autotuning.
(PID(191) turns the bit OFF automatically
when autotuning is completed.

As a Flag:
0:

Autotuning is not being executed.

1:

Autotuning is being executed.

Allowed

Bits 00 to 11
of C+9

AT Calculation Gain

Set this parameter to adjust the contribution of the
PID calculation results to the stored values.
Normally, leave this parameter set to its default
(0000).

• Increase the value when emphasizing stability.

• Decrease the value when emphasizing respon-

siveness.

0000 hex: 1.00 (Default)
0001 to 03E8 hex (1 to 1000);
(0.01 to 10.00, in units of 0.01)

Allowed
(These parameters
are read when
autotuning starts.)

C+10

Limit-cycle Hysteresis

Sets the hysteresis when the limit cycle is gener-
ated. The default setting for reverse operation
turns ON the MV with a hysteresis of SV

−20%.

Increase this setting if a proper limit cycle cannot
be generated because the PV is unstable. How-
ever, the AT accuracy will decline if the Limit-cycle
Hysteresis is higher than necessary.

0000 hex: 0.20% (Default)
0001 to 03E8 hex:
0.01 to 10.00% in units of 0.01%
FFFF hex: 0.00%

Note The percentage is with respect to the

input range.

Control data

Item

Contents

Setting range

Change with ON

input condition