2 Instructions

2-308

CP1E CPU Unit Instructions Reference Manual(W483)

High-speed Counter/Pulse Output
Instructions

INI

Applicable Program Areas

Operands

P: Port Specifier

Instruction

Mne-

monic

Varia-

tions

Function

code

Function

MODE CONTROL

INI

@INI

880

INI(880) can be used to execute the following operations

• To start comparison with the high-speed counter comparison table

• To stop comparison with the high-speed counter comparison table

• To change the PV of the high-speed counter.

• To change the PV of interrupt inputs in counter mode.

• To change the PV of the pulse output (origin fixed at 0).

• To stop pulse output.

Symbol

INI

Area

Step program areas

Subroutines

Interrupt tasks

Usage

OK

OK

OK

Operand

Description

Data type

Size

P

Port specifier

WORD

1

C

Control data

UINT

1

NV

First word with new PV

DWORD

2

P

Port

0000 hex

Pulse output 0

0001 hex

Pulse output 1

0010 hex

High-speed counter 0

0011 hex

High-speed counter 1

0012 hex

High-speed counter 2

0013 hex

High-speed counter 3

0014 hex

High-speed counter 4

0015 hex

High-speed counter 5 (Cannot be used in CP1E-E10D - )

1000 hex

PWM(891) output 0

NV: First word with new PV

INI(880)

P

C

NV

P: Port specifier

C: Control data