Motor

Baldor 2hp

Catalog

#VL3515T

12

2HP Super Dust Gorilla Owner’s Manual

O.A.S. 2007

c

XI. Wiring Diagram for Magnetic Starter (220v, 1 ** )*

*Starter will not operate at any other voltages.
**Starter is shown configured for 1O but can also be used for 2hp, 3O motors.

Always use a licensed, professional electrician.

Open access cover on the

Overload.

Set the overload amperage

dial for the SFA* amperage

of your motor. The SFA*

value can be found below:

SFA = 12.1

(FLA 11.5)

Note: Overload must be set

or nuisance tripping may

occur.

*SFA - Service Factor Amperage

*FLA - Full Load Amperage

I

O

Dedicated Receptacle Fed

from 2 Pole Dedicated Circuit

Breaker,

Magnetic Starter -

Mount Close to Collector

6’ Long Type SJT

14 AWG Power Cord

6-20P

6-20R

Optional Remote Controller diagram pg. 19

* Note: Motor Starter supplied

with system is for 220v only.

Note: This Dust Collector is

pre-wired at the factory and

need only be plugged into a

NEMA 6020R dedicated

electrical receptacle. 3hp

single phase only.