Mounting instructions, Gauge reading instructions, Air flow to filter – Oneida Air Systems Super Dust Gorilla User Manual

Page 21

Advertising
background image

20

2HP Dust Gorilla Owner’s Manual

O.A.S. 2007

c

Optional - XIX. Filter Efficiency Gauge Mounting Instructions

Can be

attached

up to 8’

away.

OR

Air Flow

to Filter

Mounting Instructions

1. Mount brass static pressure tube in plenum with tip pointed into the air stream.

Use mounting bracket and sheet metal screws if interior of plenum is not

accessible. Refer to drawings for location of brass static pressure tube.

Gauge Reading Instructions

1. Gauge may need to be zeroed. Follow the instructions provided with

pressure gauge.

3. Mount gauge up to 8’ away, mounting it closer will not affect reading.
4. Connect clear tubing from brass static pressure tube to the port labeled

“high” on the back of the pressure gauge.
5. Make sure the tubing is not crushed or kinked along its entire length, cut

shorter if necessary.

4. When the gauge rises to 3”, it’s time to clean your filter(s).

2. Take the initial reading with cleaned filter(s) and the typical number of blast

gates open in normal operation.
3. Always read the gauge with the same number of gates open. The more

gates open, the higher the pressure reading on the gauge.

Elbow Plenum

(Side View)

2. Refer to instructions provided with gauge for mounting to bracket.

After many cleaning cycles, a filter’s pressure will rise after each cleaning. An older filter does

not get as clean as a new filter.

Rectangular Plenum

Air Flow

to Filter

0

1

2 3 4

5

INCHES W.C.