Installer manual 18, Special zone types – Orbit Manufacturing Rokonet ORBIT-6 RP-206 User Manual

Page 18

Advertising
background image

Installer Manual

18

Locations: 14-21

Zone 1-8: (2

nd

Digit): Sound

Default:

2

nd

Digit Zone Sound and Comments

0

Silent
a violation during the armed period will produce no sound
the resulting alarm can still be reported to the Central Station

1

(default)

External Sounder (Continuous)
causes the external sounding device to annunciate steadily, without breaks in the
sound cadence the sound will continue until the sounder “times out” or the system is
disarmed

2

External Sounder (Pulses)
causes the external sounding device to produce a pulsed (or staggered) annunciation
this sound is usually recommended for fire alarm annunciation

3

Keypad Sounder Only
causes the piezo sounder within the system’s keypad(s) (only) to beep rapidly

4

External Sounder + Keypad Sounder
causes the external sounding device to annunciate continuously, without breaks in the
sound cadence causes the piezo sounder within the system’s keypad(s) to beep rapidly

5

External Sounder When Armed / Keypad Sounder When Disarmed
related to 24H zones
when alarm during disarm, the keypad’s buzzer will be activated
when alarm during armed system, the external sounder will be activated

6

Door Chime
assigned to an opening which, when violated during the disarmed period, will cause the
system’s keypad(s) to beep once during an alarm, the external sounding device will
annunciate continuously, without interruption. When alarm occurs during armed system
only the external sounder will be activated.

Zone

Location

Type

Sound

Z1

14

(3)

(1)

Z2

15

(5)

(1)

Z3

16

(2)

(1)

Z4

17

(6)

(1)

Z5

18

(2)

(1)

Z6

19

(2)

(1)

Z7

20

(0)

(0)

Z8

21

(0)

(0)

* (x) define the type and sound default

SPECIAL ZONE TYPES:

Location: 18 Zone 5: Fire Zone

Zone 5 is reserved as a

Fire Zone, supports four-wire Smoke Detectors. Smoke

Detector power must be interruptible in order to reset a detector “latched” in alarm. As
such it should be derived from the UO/ECL or one of the UOs terminal (see Figures 1A
and 1B). The related UO should be defined as AUX power switch.

Location: 18 Zone 5: (1

st

Digit): Type

Default: Fire

1

st

Digit

Zone Type and Comments

7

Fire
A fire zone cannot be disabled or bypassed.
A fault in the wiring to the zone will cause a Fire Trouble (fire LED blinks).
A short in the zone wiring will cause a fire alarm.