CVM1 and CV-series Controller Link Units

Section 4-4

4-4

CVM1 and CV-series Controller Link Units

The following settings are required for a Controller Link Unit when used with a
CVM1 or CV-series PLC.

4-4-1

Overview

Unit Number

Node Addresses

Setting Baud Rates

Note The factory default setting is in bold.

Always keep pins 3 and 4 set to OFF.

Terminating Resistance

Item

Switch

Page

Unit number

Unit number switch

98

Node address

Node address switch

98

Baud rate

Baud rate switch, pins 1 and 2

99

Terminating resistance

Terminating resistance switch

99

ON

CLK21

X10

1

X10

0

SW1

BD H

BD L

SHLD

RUN
ERC

M/A
LNK

TER SW

1
2
3
4

BAUD
RATE

BAUD RATE

0

0

INS
SD

M/A
LNK
RD

X10

0

NODE
NO.
X10

1

UNIT
NO.
X10

1

RSV

0

0

BIT2 BIT1

RATE

RSV

OFF OFF

2MBP

OFF ON

1MBP

ON

OFF

500KBP

NODE
NO.
X10

1

X10

0

1

2

3

4

RSV

BAUD
RATE

0

ON

3

2

14

X10

0

UNIT
NO.
X10

1

RSV

0

0

1

Setting range

Nodes

00 to 15 (default is 00)

All nodes in the Network

Setting range

Nodes

01 to 32 (default is 01)

All nodes in the Network

Switch

Baud rate

Maximum

transmis-

sion dis-

tance

Nodes

Pin 1

Pin 2

OFF

OFF

2 Mbps

500 m

Set same
rate for all
nodes in
Network.

ON

OFF

1 Mbps

800 m

OFF

ON

500 Kbps

1 km

ON

ON

Do not set.

Bottom switch

Terminating

resistance

Nodes

OFF
(factory default)

Not connected

All the nodes

Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.

ON

Connected