Appendix b memory areas, Memory areas, Appendix b – Omron CQM1H-CLK21 User Manual

Page 370: Cs/cj-series plcs, Auxiliary area

Advertising
background image

347

Appendix B

Memory Areas

This appendix provides easy reference to the words in PLC memory areas used by Controller Link Networks.

CS/CJ-series PLCs

Auxiliary Area

Network Status Flags

Bits A20200 through A20207 are turned ON to indicate that ports #0 through #7, respectively, are enabled for
the SEND(90), RECV(98), CMND(490) and PMCR. Bits A219200 through A219207 are turned ON to indicate
that an error has occurred in ports #0 through #7, respectively, during data communications using SEND(90),
RECV(98), CMND(490), or PMCR. Refer to page 189.

A203 through A210 contain the completion codes for ports #0 through #7, respectively, following data commu-
nications using SEND(90), RECV(98), CMND(490), or PMCR. Refer to page 189.

CS/CJ CPU Bus Unit Initializing Flags

Bits A30200 through A30215 turn ON while the corresponding CS/CJ CPU Bus Units (Units #0 through #15,
respectively) are initializing.

CS/CJ CPU Bus Unit Setting Error Flag and Unit Number

Bit A40203 is turned ON when the CS/CJ CPU Bus Units actually installed differ from the Units registered in
the I/O table. The unit number of the CS/CJ CPU Bus Unit involved is written to word A427.

Bits A42700 through A42715 correspond to CS/CJ CPU Bus Units #0 through #15, respectively. When a error
occurs, the bit corresponding to the unit number of the CS/CJ CPU Bus Unit involved is turned ON.

CS/CJ CPU Bus Unit Error Flag

Bit A40207 is turned ON when a parity error occurs during the transmission of data between the CPU Unit and
CS/CJ CPU Bus Units. The unit number of the CS/CJ CPU Bus Unit involved is written to word A417.

CS/CJ CPU Bus Unit Numbers

Bits A41000 through A41015 correspond to CS/CJ CPU Bus Units #0 through #15, respectively. When two
CPU Bus Units have the same unit number, the bits corresponding to the unit numbers of the CS/CJ CPU Bus
Units involved are turned ON.

Word(s)

Bit(s)

Function

A202

00 to 07

Communications Port Enabled (Network Communi-
cations Enabled) Flags

A203 to A210

00 to 15

Port #0 to #7 Completion Codes

A219

00 to 07

Port #0 to #7 Execute Error (Network Communica-
tions Execute Error) Flags

A302

00 to 15

CS/CJ CPU Bus Unit Initializing Flags

A401

13

Duplicate Number Error Flag (fatal error)

A402

03

CS/CJ CPU Bus Unit Setting Error Flag

07

CS/CJ CPU Bus Unit Error Flag

A410

00 to 15

CPU Bus Unit Duplicate Number

A417

00 to 15

CS/CJ CPU Bus Unit Error, Unit Number Flags

A427

00 to 15

CS/CJ CPU Bus Unit Setting Error Unit Number

A501

00 to 15

CS/CJ CPU Bus Unit Restart Bits

Advertising