26

Basic Procedures

Section 1-4

other PLCs in other nodes or from one PLC to IBM PC/AT or compatible com-
puters.

1-4

Basic Procedures

Preparations

C200HX/HG/HE and CQM1H-series PLCs

1,2,3...

1.

Perform mounting and wiring.

• Mount to the PLC.

• Connect the communications cables.

2.

Set the node address on the front rotary switches.

• 01 to 32

3.

Set the baud rate and operating level on the front DIP switch.

• 2 M, 1 M, or 500 Kbps

• Operating level 0 or operating level 1 (C200HX/HG/HE PLCs only)

4.

Set the terminating resistance on the sliding switch.

• ON or OFF (Only the end nodes are set to ON.)

5.

Connect power to all nodes.

6.

Connect the Programming Device to the PLC.

7.

Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
series PLCs and not necessary for CJ-series PLCs unless user-created
I/O tables have been specified).

8.

Register routing tables as required.

CVM1, CV-series, and CS/CJ-series PLCs

1,2,3...

1.

Perform mounting and wiring.

• Mount to the PLC.

• Connect the communications cables.

2.

Set the Unit number on the front rotary switches.

• 00 to 15 (0 to F: CS/CJ-series display is in hexadecimal)

3.

Set the node address on the front rotary switches.

• 01 to 32 (01 to 62) (See note a.)

4.

Set the baud rate and operating level on the front DIP switch.

• 2 M, 1 M, or 500 Kbps (wired systems only)

5.

Set the terminating resistance on the front slide switch.

• ON or OFF (Only the terminal node is set to ON.)

6.

Connect power to all nodes.

7.

Connect the Programming Device to the PLC.

8.

Create I/O tables (not necessary for C200HX/HG/HE and CQM1H-
series PLCs and not necessary for CJ-series PLCs unless user-created I/
O tables have been specified).

9.

Set the Wired Network 62 Node Enable Bit in the DM Parameter Area soft-
ware switches. (See note b.)

• ON (62 nodes max.) or OFF (32 nodes max.)

10. Register routing tables.

Note a) Setting 62 nodes is possible only with the CS1W-CLK21-V1 and

CJ1W-CLK21-V1.

The Wired Network 62 Node Enable Bit in the

DM Parameter Area software switches must be set.