Step 9. before lighting the appliance – Quadra-Fire QVI-30FB User Manual

Page 20

Advertising
background image

Quadra-Fire • QVI-30FB • 2020-900 Rev. H • 9/07

20

Step 9. Before Lighting the Appliance

Before lighting the appliance, be sure to do the following:

Remove all paperwork from the fireplace.

Review safety warnings and cautions

• Read the Safety and Warning Information section at

the beginning of this Installers Guide.

Double-check for gas leaks

• Before lighting the appliance, double-check the unit for

possible gas leaks.

Double-check vent terminations for obstructions.

• Before lighting the appliance, double-check the unit for

possible obstructions that could be blocking the vent ter-
minations.

Double-check for faulty components

• Any component that is found to be faulty MUST BE re-

placed with an approved component. Tampering with the
appliance components is DANGEROUS and voids all war-
ranties.

A small amount of air will be in the gas supply lines. When
first lighting the appliance, it will take a few minutes for the
lines to purge themselves of this air. Once the purging is
complete, the appliance will light and will operate normally.

Subsequent lightings of the fireplace will not require this
purging of air from the gas supply lines, unless the gas
valve has been turned to the OFF position
, in which
case the air would have to be purged.

NOTE: The fireplace should be run 3 to 4 hours on the initial
start-up. Turn it off and let it cool completely. Remove and
clean the glass. Replace the glass and run the fireplace for
an additional 8 hours. This will help to cure the products
used in the paint and logs.

3. Attach the low voltage wires to the ON/OFF switch lo-

cated on the front of surround.

4. Attach surround assembly by securing four corners with

screws provided (see Figure 14.) Reposition the fireplace
if necessary. Refer to surround instructions provided with
the decorative surround.

NOTE: PLACE THE THREE INSULATION PIECES INTO
THE CAVITIES AT THE BACK OF THE SURROUND BE-
FORE POSITIONING THE INSERT INTO THE FACTORY-
BUILT OR MASONRY FIREPLACE. THIS INSULATION
WILL HELP SEAL FOR COLD AIR LEAKS.

Figure 15

Figure 15 shows the minimum vertical and corresponding
maximum horizontal dimensions of mantels or other com-
bustible projections above the gas fireplace.

TOP OF

UNIT

12” MIN.

12” MAX.

MANTEL

During this break-in period it is recommended that some
windows in the house be opened for air circulation. This will
help avoid setting off smoke detectors, and help eliminate
any odors associated with the fireplace’s initial burning.

Advertising