Speed reach setting frequency, Speed reach detection band, Stall prevention during regeneration – Toshiba W7 User Manual

Page 132: Speed drop detection frequency range

Advertising
background image

126

W7 ASD Installation and Operation Manual

Speed Drop Detection Frequency Range

Program

⇒

Protection Settings

⇒

Speed Drop Detection Frequency

Range

While operating using PG feedback, this parameter sets the lower level of the
deviation limit that, once the output frequency falls below this setting, causes a
Speed Drop Detected alert.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 30.00

Units — Hz

Speed Reach Detection Band

Program

⇒

Terminal Settings

⇒

Output Terminals

⇒

Reach

⇒

Speed

Reach Detection Band

This parameter sets the bandwidth of the Speed Reach Frequency setting.

Parameter Type — Numerical

Factory Default — 2.5

Changeable During Run — Yes

Minimum — 0.0

Maximum — Max. Freq.

Units — Hz

Speed Reach Setting Frequency

Program

⇒

Output Terminals

⇒

Speed Reach Setting Frequency

This setting establishes a frequency threshold that, when reached or is within
the Reach Detection bandwidth, will provide a signal at an output terminal that
can close an appropriately configured output contact.

Parameter Type — Numerical

Factory Default — 2.5

Changeable During Run — Yes

Minimum — 0.0

Maximum — Max. Freq.

Units — Hz

Speed Reference Address

Program

⇒

Communication Settings

⇒

S20 Settings

The S20 system is Toshiba’s high-speed fiber optic communication system.
This function is unavailable at the time of this release.

Parameter Type — Selection List

Factory Default — 0

Changeable During Run — No

Speed Reference Station

Program

⇒

Communication Settings

⇒

S20 Settings

The S20 system is Toshiba’s high-speed fiber optic communication system.
This function is unavailable at the time of this release.

Parameter Type — Selection List

Factory Default — 0

Changeable During Run — No

Stall Prevention During Regeneration

Program

⇒

Protection Settings

⇒

Stall Prevention During

Regeneration

Enables/Disables the Overvoltage Stall and the Overcurrent Stall function
during regeneration only.

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Speed Drop Detection Frequency Range

Stall Prevention During Regeneration