Deceleration time #1, Dc injection on at direction change, Differential (d) gain – Toshiba W7 User Manual

Page 72: Decel time #2, Delay filter

Advertising
background image

66

W7 ASD Installation and Operation Manual

DC Injection on at Direction Change

Program

⇒

Protection Settings

⇒

DC Injection On Direction Change

Enable

This parameter Enables/Disables the use of DC Injection braking during a
change in the direction of the motor.

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Deceleration Time #1

Program

⇒

Fundamental Parameters

⇒

Fundamental #1

⇒

Deceleration Time #1

This parameter specifies the time in seconds for the ASD output to go from the
Maximum Frequency to 0.0 Hz for the #1 Deceleration profile. The accel/
decel pattern may be set using Accel/Decel #1 Pattern.

Note: A deceleration time shorter than the load will allow may

cause nuisance tripping and mechanical stress to loads.

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Decel Time #2

Program

⇒

Fundamental Parameters

⇒

Fundamental #2

⇒

Deceleration Time #2

This parameter specifies the time in seconds for the ASD output to go from the
Maximum Frequency to 0.0 Hz for the #2 Deceleration profile. The accel/
decel pattern may be set using Accel/Decel #2 Pattern.

This setting is also used to determine the deceleration rate of the Motorized
Pot
function.

Note: A deceleration time shorter than the load will allow may

cause nuisance tripping and mechanical stress to loads.

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Delay Filter

Program

⇒

Feedback Settings

⇒

Delay Filter

This parameter determines the delay in the ASD output response to the motor-
control feedback signal.

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 255

Differential (D) Gain

Program

⇒

Feedback Settings

⇒

Diff Gain

This parameter determines the degree that the differential function affects the
output signal. The larger the value entered here, the more pronounced the
Differential Gain.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 2.55

DC Injection on at Direction Change

Differential (D) Gain