Overcurrent stall level, Overload reduction starting frequency, Overtorque trip – Toshiba W7 User Manual

Page 99: Overtorque detection time, Overspeed detection frequency range

Advertising
background image

W7 ASD Installation and Operation Manual

93

Overcurrent Stall Level

Program

⇒

Protection Settings

⇒

Overcurrent Stall Level

This parameter specifies the output current level at which the output frequency
is reduced in an attempt to prevent a trip. The overcurrent level is entered as a
percentage of the maximum rating of the ASD.

Note:

Soft Stall must be enabled to use this feature.

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.00

Maximum — 200.0

Units — %

Overload Reduction Starting Frequency

Program

⇒

Protection Settings

⇒

Overload Reduction Starting

Frequency

This parameter is used to reduce the start frequency during very low-speed
motor operation. During very low-speed operation the cooling efficiency of the
motor decreases. Lowering the start frequency aides in minimizing the
generated heat.

Parameter Type — Numerical

Factory Default — 6.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 30.00

Units — Hz

Overspeed Detection Frequency Range

Program

⇒

Protection Settings

⇒

Overspeed Detection Frequency

Range

This parameter sets the upper level of the Base Frequency range that, once
exceeded, will cause an Overspeed Detected alert.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 30.0

Units — Hz

Overtorque Detection Time

Program

⇒

Protection Settings

⇒

Overtorque Detection Time

This parameter sets the amount of time that the overtorque condition may
exceed the tripping threshold level set at Overtorque Trip/Alarm Level
(Positive Torque)
and Overtorque Trip/Alarm Level (Negative Torque)

before a trip occurs.

Parameter Type — Numerical

Factory Default — 0.50

Changeable During Run — No

Minimum — 0.00

Maximum — 100.0

Units — Seconds

Overtorque Trip

Program

⇒

Protection Settings

⇒

Overtorque Trip

This parameter Enables/Disables the Over Torque Tripping function.

When enabled, the ASD trips if an output torque larger than the setting of
parameters Overtorque Trip/Alarm Level (Positive Torque) or Overtorque
Trip/Alarm Level (Positive Torque)
is detected for a time longer than the
setting of the Overtorque Detection Time parameter.

When disabled, the ASD does not trip due to overtorque conditions.

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Overcurrent Stall Level

Overtorque Trip