Command mode, Break/make auto restart, Commercial (power) hold time – Toshiba W7 User Manual

Page 67: Brake fault internal timer

Advertising
background image

W7 ASD Installation and Operation Manual

61

Brake Fault Internal Timer

Program

⇒

Protection Settings

⇒

Brake Fault Internal Timer

After a brake failure has occurred, the user-set Brake Fault Time clock setting
will begin to count down. Once this time has elapsed, a signal will be provided
to indicate that the brake has failed.

This signal may be used to halt a related system or to notify the user.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 10.00

Units — Seconds

Break/Make Auto Restart

Program

⇒

Protection Settings

⇒

Break/Make (Auto Retry)

Enables/Disables the ability of the drive to start into a spinning motor when the
ST-to-CC connection momentarily opens and is then closed (Break/Make ST)
or after a power interruption (momentary power failure).

Settings:

Off
Power Failure
Make/Break ST
Both

Parameter Type — Selection List

Factory Default — Off

Changeable During Run — No

Command Mode

Program

⇒

Utilities

⇒

Command and Frequency Settings

⇒

Command

Mode Select

The Command Mode Selection establishes the source of the command input
for the ASD. Command inputs include Run, Stop, Forward, etc.

Settings:

(Use) (Control Terminal Strip) Terminal Block
(Use) LED Keypad
(Use) Common Serial (TTL)
(Use) RS232/RS485
(Use) Communication Card

Parameter Type — Selection List

Factory Default — Terminal Block

Changeable During Run — No

Commercial (Power) Hold Time

Program

⇒

Special Control

⇒

Commercial Hold Time

This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-drive-output criteria has
been met.

Parameter Type — Selection List

Factory Default — 2.00

Changeable During Run — No

Minimum — 0.10

Maximum — 10.00

Units — Seconds

Brake Fault Internal Timer

Commercial (Power) Hold Time