Earth fault alarm level, Earth fault alarm time, Earth fault trip level – Toshiba W7 User Manual

Page 75

Advertising
background image

W7 ASD Installation and Operation Manual

69

Earth Fault Alarm Level

Program

⇒

Protection Settings

⇒

EF Alarm Level

This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Alarm activation criteria.

Parameter Type — Numerical

Factory Default — 100

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Units — %

Earth Fault Alarm Time

Program

⇒

Protection Settings

⇒

EF Alarm Delay

In the event that the Earth Fault Alarm activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the Earth Fault Alarm is
activated.

This parameter sets the start-time of the count-down timer.

Parameter Type — Numerical

Factory Default — 1.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 2.50

Units — Seconds

Earth Fault Trip Delay

Program

⇒

Protection Settings

⇒

EF Trip Delay

In the event that the Earth Fault Trip activation criteria is met, a timer begins
to count down to zero. Upon reaching zero, the Earth Fault Trip is activated.

This parameter sets the start-time of the count-down timer.

Parameter Type — Numerical

Factory Default — 1.0

Changeable During Run — Yes

Minimum — 0.00

Maximum — 2.50

Units — Seconds

Earth Fault Trip Level

Program

⇒

Protection Settings

⇒

EF Trip Level

This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Trip activation criteria.

Parameter Type — Numerical

Factory Default — 1.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 1.00

Units — %

Earth Fault Alarm Level

Earth Fault Trip Level