Toshiba Multiprotocol Ethernet Interface for Toshiba G9/VFAS1 Adjustable Speed Drives ASD-G9ETH User Manual

Page 112

Advertising
background image

111

ICC

BO5 ...... Enables or disables process (PID) feedback control. Note that this object

does not activate (turn on) feedback control. It only enables or disables
feedback control once it has already been activated. ASD parameter FA06,
bit#5.

BO6 ...... Communication interface frequency priority selection. Allows the frequency

command from the interface card to be used by the drive without having to
set the Frequency Mode parameter. Refer to the Toshiba documentation
regarding "Command Mode and Frequency Mode Control" for detailed
information pertaining to the frequency source hierarchy and the use of
overrides. ASD parameter FA06, bit#14.

BO7 ...... Communication interface command priority selection. Allows commands

(BO1, BO2, and BO5) from the interface card to be used by the drive
without having to explicitly set the Command Mode parameter. Refer to the
Toshiba documentation regarding "Command Mode and Frequency Mode
Control" for detailed information pertaining to the command source
hierarchy and the use of overrides. ASD parameter FA06, bit#15.

BO8 ...... Output terminal data out 1. Any programmable output terminals that are

configured to output “specified data output 1” will follow the value of this BO.
ASD parameter FA50, bit#0.

BO9 ...... Output terminal data out 2. Any programmable output terminals that are

configured to output “specified data output 2” will follow the value of this BO.
ASD parameter FA50, bit#1.

BO10 .... Output terminal data out 3. Any programmable output terminals that are

configured to output “specified data output 3” will follow the value of this BO.
ASD parameter FA50, bit#2.



Analog Input Objects

AI1 ........ Output frequency in 0.01Hz units. ASD parameter FD00.

AI2 ........ Load current in 0.01% units (10000=100.00%=drive's rated current). ASD

parameter FE03.

AI3 ........ Output voltage in 0.01% units (10000=100.00%=drive's rated voltage).

ASD parameter FE05.

AI4 ........ Input power consumption (drive+motor) in 0.01kW units. ASD parameter

FE29.

AI5 ........ Indicates the signal level currently being applied to the ASD's RR analog

input terminal. This can be used to monitor such items as feedback sensor
outputs and other process variables. Expressed in 0.01% units
(10000=100.00%=input rated value). ASD parameter FE35.

AI6 ........ Similar to AI5, this object indicates the signal level currently being applied to

the ASD's VI/II analog input terminal. ASD parameter FE36.

AI7 ........ Similar to AI5, this object indicates the signal level currently being applied to

the ASD's RX analog input terminal. ASD parameter FE37.

Advertising