Parameter numbering – Toshiba Multiprotocol Ethernet Interface for Toshiba G9/VFAS1 Adjustable Speed Drives ASD-G9ETH User Manual

Page 23

Advertising
background image

22

ICC

9. Parameter Numbering

Inspection of the Toshiba ASD user’s manual reveals that the ASD’s parameters are
organized as hexadecimal numbers ranging from F000 to FFFF. These parameters
are made accessible to the interface board as “registers”, and are numerically
remapped to present a more natural interface to the communications user. There
are 1500 total registers available via the interface board, and their mappings are as
shown in Table 1.

Table 1: ASD Parameter-to-Register Mapping

Hexadecimal ASD

Parameter Numbers…

…Map to Decimal Register

Numbers

F000 - F999

1 - 1000

FA00 - FA99

1001 - 1100

FB00 - FB99

1101 - 1200

FC00 - FC99

1201 - 1300

FD00 - FD99

1301 - 1400

FE00 - FE99

1401 - 1500


This mapping is easier to understand if one just uses the interface's web page as a
guide (refer to Figure 6 and section 10.4.4). The "parameter” numbers (ASD
references) and "register” numbers (network references) for all available parameters
are shown in the first two columns. Commanding the drive over the network
therefore entails writing to registers 1007 (option board command 1) and 1008
(option board frequency command), which correspond to ASD parameters FA06 and
FA07, respectively.

Figure 6: Web Page Register Assignment Reference

Advertising