Owner’s manual, Troubleshooting, Continued – Vanguard Managed Solutions PRVYS18PWA User Manual

Page 19

Advertising
background image

19

104343

OWNER’S MANUAL

TROUBLESHOOTING

Continued

OBSERVED PROBLEM

Burner does not light after ODS/pilot is lit

Delayed ignition burner

Burner backfiring during combustion

Slight smoke or odor during initial operation

Heater produces a whistling noise when
burner is lit

Moisture/condensation noticed on windows

Dark residue on logs or inside or fireplace

REMEDY

1. Contact local natural gas company
2. Clean burner (see Cleaning and Mainte-

nance, page 23) or replace burner orifice

3. Replace burner orifice

1. Contact local propane/LP gas company
2. Clean burner (see Cleaning and Mainte-

nance, page 23) or replace burner orifice

1. Clean burner (see Cleaning and Mainte-

nance, page 23) or replace burner orifice

2. Replace damaged burner
3. Replace gas regulator

1. Check burner for dirt and debris. If

found, clean burner (see Cleaning and
Maintenance
, page 23)

2. Replace gas regulator
3. Problem will stop after a few hours of

operation

1. Turn control knob to LO position and

let warm up for a minute

2. Operate burner until air is removed from

line. Have gas line checked by local
natural gas company

3. Observe minimum installation clear-

ances (see pages 7 through 9)

4. Clean burners (see Cleaning and Mainte-

nance, page 23) or replace burner orifice

1. Refer to Air for Combustion and Venti-

lation requirements (pages 4 through 6)

1. Properly locate logs (see Installing Logs,

page 14)

2. Eliminate source of drafts around heater

3. Clean out air holes at burner inlet. Peri-

odically repeat as needed

4. Remove blockage or replace burner

POSSIBLE CAUSE

1. Inlet gas pressure is too low
2. Burner orifice clogged

3. Burner orifice diameter is too small

1. Manifold pressure is too low
2. Burner orifice clogged

1. Burner orifice is clogged or damaged

2. Damaged burner
3. Gas regulator defective

1. Not enough air

2. Gas regulator defective
3. Residues from manufacturing processes

and logs curing

1. Turning control knob to HI position

when burner is cold

2. Air in gas line

3. Air passageways on heater blocked

4. Dirty or partially clogged burner orifice

1. Not enough combustion/ventilation air

1. Improper log placement

2. Drafts or other air currents affecting

flame pattern

3. Air holes at burner inlet blocked

4. Burner flame holes blocked

Continued