Input:debounce – VXI VM4016 User Manual

Page 26

Advertising
background image

VXI Technology, Inc.

26

VM4016 Programming

INPUT:DEBOUNCE

The INPut:DEBounce command sets the time period for the digital debounce circuitry. This
command affects all the 16 channels of the instrument. It is important to note that the debounce
resolution is 9.6 µs.

INPut:DEBounce <value>

Where <value> ranges from 9.6 µs, i.e.,
0.0000096 s to 0.6291456 s.

EXAMPLES


INPut:DEBounce 9.6e-6

Sets the input debounce time for all
channels to 0.0000096 s. This will not allow
a signal to generate an interrupt unless the
input signal crosses the signal for more than
9.6 e-6 seconds.


INP:DEB 0.6

Setting input debounce time to 0.6 s.


INP:DEB?

Returns the input debounce time as 0.6 s.

0.6

Advertising