Troubleshooting – Vanguard Heating VN18A User Manual

Page 21

Advertising
background image

www.desatech.com

21

113052-01A

TROUBLESHOOTING

Continued

POSSIBLE CAUSE

1. Control knob not fully pressed in
2. Control knob not pressed in

long enough

3. Equipment shutoff valve not

fully open

4. Thermocouple connection

loose at control valve

5. Pilot flame not touching ther-

mocouple, which allows ther-
mocouple to cool, causing pi-
lot flame to go out. This prob-
lem could be caused by one or
both of the following:
A) Low gas pressure
B) Dirty or partially clogged
ODS/pilot

6. Thermocouple damaged
7. Control valve damaged
8. Safety interlock system has

been triggered (thermostat
models only)

1. Burner orifice(s) is clogged

2. Inlet gas pressure is too low

1. Manifold pressure is too low

2. Burner orifice(s) is clogged

1. Burner orifice(s) is clogged or

damaged

2. Burner damaged
3. Gas regulator defective

1. Plaque damaged
2. Inlet gas pressure is too low

3. Control knob set between

locked positions

1. Residues from manufacturing

processes

REMEDY

1. Press in control knob fully
2. After ODS/pilot lights, keep con-

trol knob pressed in 30 seconds

3. Fully open equipment shutoff

valve

4. Hand tighten until snug, then

tighten 1/4 turn more

5. A) Contact local natural or

propane/LP gas company
B) Clean ODS/pilot (see
Cleaning and Maintenance,
page 19) or replace ODS/pi-
lot assembly

6. Replace pilot assembly
7. Replace control valve
8. Wait one minute for safety in-

terlock system to reset. Repeat
ignition operation

1. Clean burner orifice(s) (see

Cleaning and Maintenance,
page 19) or replace burner
orifice(s)

2. Contact local natural or pro-

pane/LP gas company

1. Contact local natural or pro-

pane/LP gas company

2. Clean burner orifice(s) (see

Cleaning and Maintenance,
page 19) or replace burner
orifice(s)

1. Clean burner orifice(s) (see

Cleaning and Maintenance,
page 19) or replace burner
orifice(s)

2. Replace burner
3. Replace gas regulator

1. Replace burner
2. Contact local natural or pro-

pane/LP gas company

3. Turn control knob until it

locks at desired setting

1. Problem will stop after a few

hours of operation

OBSERVED PROBLEM

ODS/pilot lights but flame goes
out when control knob is re-
leased

Burner(s) does not light after
ODS/pilot is lit

Delayed ignition of burner(s)

Burner backfiring during com-
bustion

Burner plaque(s) does not glow

Slight smoke or odor during ini-
tial operation