Air for combustion and ventilation, Continued, Ventilation air – Vanguard Heating VN18A User Manual

Page 6

Advertising
background image

www.desatech.com

113052-01A

6

1.

Determine the volume of the space (length x
width x height).

Length x Width x Height =__________cu. ft.
(volume of space)

Example:

Space size 20 ft. (length) x 16 ft.

(width) x 8 ft. (ceiling height) = 2560 cu. ft. (vol-
ume of space)

If additional ventilation to adjoining room is sup-
plied with grills or openings, add the volume of
these rooms to the total volume of the space.

2.

Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

Example:

2560 cu. ft. (volume of space) x 20 =

51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in
the space.

Vent-free heater

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________ Btu/Hr

Gas fireplace logs

__________ Btu/Hr

Other gas appliances* + __________ Btu/Hr

Total = __________ Btu/Hr

* Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors
and vents to the outdoors.

Example:

Gas water heater

______________ Btu/Hr

Vent-free heater

______________ Btu/Hr

Total

______________ Btu/Hr

4.

Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.

________ Btu/Hr (maximum the space can support)

________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space
can support)

60,000 Btu/Hr (actual amount of
Btu/Hr used)

The space in the above example is a confined space
because the actual Btu/Hr used is more than the maxi-
mum Btu/Hr the space can support. You must pro-
vide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an uncon-
fined space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation
Air From Inside Building.

B. Vent room directly to the outdoors. See Ventila-

tion Air From Outdoors, page 7.

AIR FOR COMBUSTION

AND VENTILATION

Continued

C. Install a lower Btu/Hr heater, if lower Btu/Hr size

makes room unconfined.

If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support, the space is an uncon-
fined space. You will need no additional fresh air ven-
tilation.

WARNING: If the area in

which the heater may be oper-
ated is smaller than that defined
as an unconfined space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air
by one of the methods described
in the

National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section
5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un-
confined space. When ventilating to an adjoining
unconfined space, you must provide two perma-
nent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting
the two spaces (see options 1 and 2, Figure 2).
You can also remove door into adjoining room (see
option 3, Figure 2). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation
for required size of
ventilation grills or ducts.

40,000

+ 20,000

= 60,000

Figure 2 - Ventilation Air from Inside

Building

Or

Remove

Door into
Adjoining

Room,

Option 3

Ventilation Grills

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room,

Option 1

Advertising
This manual is related to the following products: