Head Pressure Control, Low Ambient Control Switch:

The switch is used to cycle the condenser fan at low ambient temperature condition. Set the switch

to 170 psig for cut-in and 70 psig for the differential. Further adjustment may be needed. Verify

the settings via refrigeration manifold gauge and perform the final adjustments to the readings on

the gauge manifold.

Condensing Unit

* Low ambient control is in the control box

-11-

High Pressure
Cutout

Low Ambient
Control*

Low Pressure
Cutout