Water piping — single-zone system, Gold cgs gas-fired water boiler — boiler manual, Diaphragm-type or bladder- type expansion tank – Weil-McLain GOLD CGS 550-110-260/0107 User Manual

Page 15: Closed-type expansion tank

Advertising
background image

Part number 550-110-260/0107

15

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Water piping — single-zone system

3b

Figure 4

Diaphragm- or bladder-type expansion tank

Piping to single-zone system

See Table 3 for piping sizes.

Figure 5

Closed-type expansion tank

Piping to single-zone system

See Table 3 for piping sizes.

Diaphragm-type or bladder-
type expansion tank

(Figure 4)

1. Ensure expansion tank size will handle boiler and

system water volume and temperature. Tank must

be located in boiler return piping as close to boiler

as possible, before inlet side of circulator. See tank

manufacturer’s instructions for details.

. Install an

automatic air vent

in air vent tapping as

shown.

Closed-type expansion tank

(Figure 5)

1. Ensure expansion tank size will handle boiler and

system water volume and temperature. See tank

manufacturer’s instructions for details.

. Connect tank to ½” NPT tapping located behind

supply outlet, using ½” NPT piping. Pitch any

horizontal piping up towards tank 1 inch per 5 feet

of piping.

Undersized expansion tanks cause system water to be lost from relief valve and makeup water

to be added through fill valve. Eventual section failure can result.

Use

Figure 4

or

Figure 5

only for single-zone systems designed for return water at least 130°F.

For systems with low return water temperature possible, such as converted gravity systems

and radiant heating systems, refer to the special piping suggestions of pages 18-3. Failure to

prevent low return water temperature to the boiler could cause corrosion of the boiler sections

or burners, resulting in severe personal injury, death or substantial property damage.

Advertising