Water piping — multiple zones, Gold cgs gas-fired water boiler — boiler manual – Weil-McLain GOLD CGS 550-110-260/0107 User Manual

Page 17

Advertising
background image

Part number 550-110-260/0107

1

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Figure 6

Zoning with circulators

— return water 130°F or higher.

Figure 7

Zoning with zone valves

— return water 130°F or higher.

1

Boiler isolation (balancing)

valves

2

Flow/check valve

3

System or zone circulator

5

Zone valve

6

Drain valve

9

Relief valve

10

Automatic air vent (with diaphragm-type expansion tank), or connect

to tank fitting (closed-type expansion tank).

DO NOT

use an automatic

air vent when using closed-type expansion tank. It would allow air to

leave the system, causing waterlogging of the expansion tank.

11

Fill valve

12

Diaphragm-type or bladder-type expansion tank, if used (For closed-

type expansion tank, pipe from top of air separator to tank fitting as in

Figure 5

, page 15.)

13

Air separator and automatic vent, if used (Note that the fill valve must

always be connected to the expansion tank, regardless of location of

expansion tank circulator or air separator.

3c

Water piping — multiple zones

(continued)

For systems with possible low return-water temperature (such as converted gravity systems,

radiant heating systems and heat pump systems), refer to the special piping suggestions of

Figures 8 - 12

, as applies. Failure to prevent sustained low return water temperature to the

boiler could cause corrosion of the boiler sections, resulting in severe personal injury, death

or substantial property damage.