Start-up — preparation, Gold cgs gas-fired water boiler — boiler manual, Fill the system with water – Weil-McLain GOLD CGS 550-110-260/0107 User Manual

Page 27: Determine if water treatment is needed, Freeze protection (when used), Check for gas leaks

Advertising
background image

Part number 550-110-260/0107



GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Start-up — preparation

7a

Fill the system with water

1. Close manual and automatic

air vents

and

boiler drain cock.

.

Fill to correct system pressure

. Correct

pressure will vary with each application.

Typical cold water fill pressure for a residential

system is 1 psi.

3.

Purge air

from system:

a. Connect a hose to the purge valve (see

drain valves, item

6

, in suggested piping

diagrams on pages 1 through 1,

Fig-

ure 6

through

Figure 11

). Route hose

to an area where water can drain and be

seen.

b. Close the boiler or system isolation

valve between the purge valve and fill

connection to the system.

c. Close zone isolation valves.
d. Open quick-fill valve on cold water

makeup line.

e. Open purge valve.
f. One zone at a time, open the isolation

valves. Allow water to run through the

zone, pushing out the air. Run until no

noticeable air flow is present. Close the

zone isolation valves and proceed with

the next zone. Follow this procedure

until all zones are purged.

g. Close the quick-fill water valve and

purge valve and remove the hose. Open

all isolation valves. Watch that system

pressure rises to correct cold-fill pres-

sure.

h. After the system has operated for a

while, eliminate any residual air by

using the manual air vents located

throughout the system.

i. If purge valves are not installed in

system, open manual air vents in system

one at a time, beginning with lowest

floor. Close vent when water squirts out.

Repeat with remaining vents.

4. Open

automatic air vent

(diaphragm-type

or bladder-type expansion tank systems only)

one turn.

5. Open other vents:

a. Starting on the lowest floor, open air

vents one at a time until water squirts

out.

b. Repeat with remaining vents.

6. Refill to correct pressure.

Determine if water treatment is needed

Do not use

petroleum-based cleaning or sealing com-

pounds

in boiler system. Severe damage to boiler will occur,

resulting in substantial property damage.

Eliminate all system leaks. Continual fresh makeup water will

reduce boiler life. Minerals can build up in sections, reduc-

ing heat transfer, overheating cast iron, and causing section

failure.

Verify water chemistry

Consult local water treatment companies for unusually hard water areas (above

 grains hardness) or low pH water conditions (below .0). Boiler water pH of
.0 to 8.5 is recommended.

Freeze protection (when used)

Use antifreeze made especially for hydronic systems. Inhibited propylene glycol

is recommended.

Do not use

ethylene glycol, automotive or undiluted anti-

freeze

. Severe personal injury or death can result.

1. Determine

antifreeze quantity

according to system water content. Boiler

water content is listed on page 63. Remember to include expansion tank water

content.

. Follow antifreeze manufacturer’s instructions.
3. A 50% solution of propylene glycol/water provides maximum protection to

about -30°F.

4. Local codes may require

back flow preventer

or actual disconnect from city

water supply.

5. When using antifreeze in a system with automatic fill, install a water meter

to monitor water makeup. Glycol will leak before the water begins to leak,

causing glycol level to drop. Added water will dilute the antifreeze, reducing
the freeze protection level.

Check for gas leaks

Before starting the boiler, and during initial operation, smell

near the floor and around the boiler for gas odorant or any

unusual odor. Do not proceed with start-up if there is any

indication of a gas leak. Repair any leak at once.

Propane boilers only

— Your propane supplier mixes an

odorant with the propane to make its presence detectable.

In some instances, the odorant can fade and the gas may no

longer have an odor.
• Propane gas can accumulate at floor level. Smell near the

floor for the gas odorant or any unusual odor. If you suspect

a leak, do not attempt to light the pilot.

• Use caution when attempting to light the propane pilot.

This should be done by a qualified service technician, par-

ticularly if pilot outages are common.

• Periodically check the odorant level of your gas.

• Inspect boiler and system at least yearly to make sure all

gas piping is leak-tight.

• Consult your propane supplier regarding installation of a

gas leak detector. There are some products on the market

intended for this purpose. Your supplier may be able to

Advertising