Troubleshooting — control module lights, Gold cgs gas-fired water boiler — boiler manual – Weil-McLain GOLD CGS 550-110-260/0107 User Manual

Page 53

Advertising
background image

Part number 550-110-260/0107

53

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Troubleshooting — control module lights

(cont.)

11d

CHART 7 — Insufficient heat or no heat to system (POWER light on steady)

Electrical shock hazard — Wherever you see

TURN OFF POWER , follow the instructions. Failure to follow

instructions could result in severe personal injury, death or substantial property damage.

• Replace rollout switch.

• Boiler is in standby.

• Set thermostat to call for

heat and recheck

operation.

• Verify

Sequence of

operation, Figure 18,

page 31.

Replace control module.

Retest.

• Boiler water temperature exceeded

setting on limit switch with thermostat

calling for heat. Boiler is OK. (See normal

sequence of operation,

Figure 18, p. 31.)

• Also check setting on limit switch (should

be above 140°F.).

• Has it been at least 5 minutes since setting thermostat to

call for heat? If not, wait 5 minutes. Is system heating?

• Is thermostat set to call for heat? Remove thermostat

wires at boiler and check continuity across the two wires.

If circuit isn't closed, check external thermostat (zone

valve, relay, etc.) wiring. Correct problems and retry.

• Reconnect external thermostat wiring at boiler.

Is thermostat circuit closed (continuity across wires)?

• If you have sufficient heat — boiler should be in normal

operating sequence. (See normal sequence of operation,

Figure 18, page 31.)

• If you have less than sufficient heat —

Is vent or combustion air piping free of blockage?

No

Yes

• Correct conditions and

recheck operation.

• See

Figure 18, page 31

for normal sequence of

operation.

Contact your Weil-McLain

sales representative.

• Replace control

module.

• Retest.

• Repair/replace

circulator. Retest.

• Repair/replace

wiring. Retest.

• Remove CIRCULATOR harness plug from

CIRCULATOR plug receptacle (Figure 25, Item

7, page 46). Check with voltmeter across pins of

control module receptacle.

Does voltmeter show 120 VAC across pins?

No

Yes

Is boiler System circulator operating?

• Wait 5 minutes.

Is

FLAME light on?

No

Yes

• Wait for boiler water to cool to temperature 20 to 30 °F

lower than temperature set on limit switch.

Are limit switch contacts closed?

Is

LIMIT light on?

No

Yes

Are all red lights off?

No

Yes

Wait 30 seconds.

Are all red lights off?

No

Yes

• Replace control module.

• Retest.

• Check limit switch

contacts with continuity

checker.

Are limit switch contacts

closed?

No

Yes

No

Yes

No

Yes

• Replace

limit switch.

• Retest.

No

Yes

Check rollout switch

continuity — is switch

closed?

No

Yes

• Check any other

limit controls wired

into the limit

circuit. If all are

OK, then replace

control module.

• Retest.

If rollout thermal fuse element has

opened, determine cause and

correct condition. Failure to do so

will cause severe personal injury,

death or substantial property

damage.

Advertising