Ratings, Gold cgs gas-fired water boiler — boiler manual – Weil-McLain GOLD CGS 550-110-260/0107 User Manual

Page 63

Advertising
background image

Part number 550-110-260/0107

63

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Ratings

Table 7 Boiler ratings

DOE

13b

(Note 5)

CGs boilers for residential radiant panel systems, converted gravity heating systems or other low water tempera-

ture applications should be installed with balancing valves and bypass piping equal to the supply and return
size to avoid excessive flue gas condensation due to lower operating water temperatures. For alternate piping,
contact your Weil-McLain sales office. CSA design certified for installation on combustible flooring. Tested for
50 psi working pressure.

Boiler

model

number

DOE

Heating

capacity

(Btuh)

0-2,000 feet

2,000-4,500 feet

Net

I=B=R

ratings

(Btuh)

Boiler

water

content
(gallons)

DOE

Seasonal

efficiency

(% AFUE)

Vent

size

Input

(Btuh)

Output

(Btuh)

Input

(Btuh)

Output

(Btuh)

(Note 1)

(Note 2)

(Note 3)

(Note 5)

(Note 4)

CGs-3

(Note 5)

57,000

67,000

57,300

60,300

51,600

50,000

1.5

85.3

3"

CGs-4

85,000

100,000

85,000

90,000

76,500

74,000

2.1

84.6

3"

CGs-5

112,000

133,000

112,400

119,000

100,600

97,000

2.7

84.0

3"

CGs-6

140,000

167,000

140,300

150,300

126,300

122,000

3.3

83.4

3"

Notes

1. Add “PIN” for natural gas boiler - “PIL” for propane gas boiler.

2. Based on standard test procedures prescribed by the United States Department of Energy.

3. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building

and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance
of 1.15. An additional allowance should be made for unusual piping and pickup loads.

4. CGs boilers require special venting, consistent with Category III or IV boiler. Use only the vent materials and

methods specified in CGs vent supplements. CGs boilers may be direct-vented (using 3” diameter air piping)
as specified in the direct vent supplements.

5. As an Energy Star Partner, Weil-McLain has determined that the CGs-3 meets the Energy Star guidelines for

energy efficiency.