Display alarm codes – WhisperKool 081310 User Manual

Page 17

Advertising
background image

Page 15

CPSM

Mode

(Cont.)

CCS – Cellar Pre-Chill Set Point: This parameter is set at 52°f, but can be adjusted to a set point

between 45°f - 67°f.

bLL/Act – Compressor Off or On for Low (bLL) or High (Act) Temperature Alarm: These param-

eters are set at “n”. With this parameter set at “n” the refrigeration system will continue to operate

normally, if there is a High or Low temperature Alarm. To change this parameter, change the set-

ting to “y”, and the compressor/refrigeration system will shut off during a High or Low tempera-

ture Alarm.

Con/Cof – Compressor On time (Con) and Off time (Cof) with a Probe 1 failure/Alarm. These

parameters are set at Con 40 min/Cof 10 min. In the event that there is a Probe 1 failure/Alarm,

the compressor/refrigeration system automatically starts a predetermined ON/OFF cycle, which

is controlled by the Con and the Cof parameters. The customer can adjust these parameters to

maintain the desired Bottle Probe temperature. During a Probe 1 failure/Alarm, the Bottle Probe

temperature can be monitored by pressing the Up or Down arrow to view the High and Low

Temperature History.

Hes – Differential for Energy Reduction – This parameter is set at 4, which results in a set point

of 58°f during the Energy Reduction mode. A decrease in this setting will decrease the set point,

and an increase in this feature will increase the set point.

Display Alarm Codes

Message

Cause

Outputs

“P1”

Room probe failure

Compressor output acc. to par. “Con” and “COF”

“P2”

Evaporator probe failure

Defrost end is timed

“HA”

Max bottle probe temp alarm

Outputs unchanged

“LA”

Min bottle probe temp alarm

Outputs unchanged

“EA”

External alarm

Outputs unchanged

Advertising