If the breaker remains set, check to see if compressor is

running and condenser fan turns on.

After compressor runs a few minutes, check the refrigerant

“sight glass” in the ¼” copper tubing. Look for bubbles.

If no bubbles are present and compressor is running,

refrigerant system is running OK.

If bubbles are present, system is low on refrigerant.

A CERTIFIED HVAC service technician will have to locate and

repair any refrigerant leaks, then add refrigerant.

Condenser fan should come on either immediately on

compressor start or after sight glass gets warm.

If not, compressor will trip off on high pressure safety

control, reducing capacity and possibly tripping the

breaker.

In this event, CERTIFIED HVAC service technician will have

to check for the problem.

Compressor runs intermittently

1. Evaporator Unit

blower not running with

compressor

Evaporator coil will probably be iced.

Call a CERTIFIED HVAC service technician.

2. Evaporator Unit

blower running too slow

or air flow blocked.

• Increase speed control setting if equipped.

• Clean coil if necessary, remove obstructions.

• Coil icing can occur.

3. Condenser coil

blocked with dirt or

other matter.

Clean coil and fan thoroughly, clear any obstructions and/

or cause for hot air recirculation.

4. Condenser fan

motor bearings faulty

causing motor to trip on

overload, followed by

compressor cycling off.

Call a CERTIFIED HVAC service technician to diagnose and

repair.

5. Hot air, above 125°,

entering condenser from

confined space (outer

room)

Provide source of cool air to condenser space in accordance

with directions in this manual.

6. System refrigerant

overcharge.

Call a CERTIFIED HVAC service technician to diagnose and

recover excess refrigerant.