TROUBLESHOOTING

Fault

Cause

Solution

Water leaking from unit

1. Condensate drain

clogged

Clear out drain

2. Evaporator coil

frozen

Clean the coil and / or fan wheel

3. Drain line improperly

installed

Call a CERTIFIED HVAC service technician.

Wine cellar temperature above thermostat set point

1. Large quantity of warm

wine placed in cellar

Allow time for wine to cool

2. Wine Cellar Door left

open for long period.

Close Door. Allow time for wine to cool.

3. No power to either

evaporator or condensing

unit

Is the thermostat display illuminated?

If not, check power supply switch, if equipped. Ensure it is in the

ON position.

If on, check to see in the breaker is tripped.

If tripped, reset and check display.

Check breaker to condensing unit. If tripped, check to see if com-

pressor is hot – too hot to touch. If so, allow to cool for one (1)

hour before resetting breaker.

After cooling, reset breaker and note whether it remains set or

trips off. If it trips, call a CERTIFIED HVAC service technician for

repair.

Display Alarm Codes

Message

Cause

Outputs

“P1”

Room probe failure

Compressor output acc. to par. “Con” and “COF”

“P2”

Evaporator probe failure

Defrost end is timed

“HA”

Max bottle probe temp alarm

Outputs unchanged

“LA”

Min bottle probe temp alarm

Outputs unchanged

“EA”

External alarm

Outputs unchanged