Thermostat wiring diagram, Branch circuit sizing guide, Watt load – Whirlpool Energy Smart 188414 User Manual

Page 23: Recommend over current protection rating

Advertising
background image

23

ELECTRONIC

THERMOSTAT (ET)

FUSED DISCONNECT

OR CIRCUIT BREAKER

L 1

L 3

L 4

T 4

T 2

TEMPERATURE

SENSOR

UPPER

ELEMENT

LOWER

ELEMENT

319165-000G

ENERGY SMART

MODULE (ESM)

GROUND

SCREW

ELECTRICAL

SERVICE

GROUND

RED

BLACK

BLUE

BLUE

BLACK

YELLOW

ON

BRACKET

ON

JUNCTION

BOX COVER

BLACK - 5 WIRES

BLACK - 2 WIRES

120

V

1500*
2000
2500
3000
3500
4000
4500
5000
5500

15
20
30
30

-
-
-
-
-

WATT

LOAD

BRANCH CIRCUIT SIZING GUIDE

Based on N.E.C. NFPA NO. 70 - 1999

15
15
15
20
20
25
30
30

15
15
15
15
20
20
25
30
30

208

V

240

V

Recommend

Over Current

Protection Rating

12
10
10

8

-
-
-
-
-

14
14
14
12
10
10
10
10

14
14
14
12
12
10
10
10
10

120

V

208

V

240

V

Copper Wire Size

AWG Based on

N.E.C.

Table 310 - 16

C)

Wattages less than 1500 may be wired 14 gage with a maximum

15 amp protection.

SMART GRID

WIRE HARNESS

GREEN

BLACK

RED

THERMOSTAT WIRING DIAGRAM

Advertising