262292-YTG-B-0107

Unitary Products Group

11

NOTE:All gas units are two-stage heating.

First stage is 50% of total.
S.S.E. = Steady State Efficiency (80%) - output divided by input.

TABLE 1: SOUND POWER RATING

1

UNIT

SIZE

CFM

ESP

BLOWER

SOUND POWER (db 10

-12

Watts)

Octave Band Centerline Frequency (Hz)

SWL

dB(A)

dB(A)

@

10Ft.

2

IWG

RPM

BHP

63

125

250

500

1,000

2,000

4,000

8,000

WR180

6,000

1.00

1,080

4.60

99

99

89

82

84

77

72

67

89

56

WR240

8,000

1.00

1,120

6.65

102

102

92

85

87

80

75

70

92

59

WR300

10,000

1.30

1160

12.5

108

108

98

91

93

86

81

76

98

65

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA

values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture
has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA
value or sound data in any other form than sound power level ratings.

2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360)

1

1. Certified in accordance with the Unitary Large Equipment

certification program which is based on ARI Standard 340/
360.

MODEL

MBH

EER

2

2. EER = Energy Efficiency Ratio at full load - the cooling

capacity in Btu’s per hour (Btuh) divided by the power input in
watts, expressed in Btuh per watt (Btuh/watt).

IPLV

3

3. IPLV = Integrated Part Load Value.

COOLING ONLY

WR180C/E00

180

11.9

12.7

WR240C/E00

240

11.0

11.3

WR300C/E00

300

10.0

10.6

COOLING WITH GAS HEAT

WR180N/S

180

11.9

12.7

WR240N/S

240

11.0

11.3

WR300N/S

300

10.0

10.6

COOLING WITH ELECTRIC HEAT

WR180E18

180

11.9

12.7

WR180E36

180

11.9

12.7

WR180E54

178

11.7

12.5

WR180E72

178

11.7

12.5

WR240E18

240

11.0

11.3

WR240E36

240

11.0

11.3

WR240E54

238

10.8

11.1

WR240E72

238

10.8

11.1

WR300E18

300

10.0

10.6

WR300E36

300

10.0

10.6

WR300E54

298

9.8

10.4

WR300E72

298

9.8

10.4

TABLE 3: GAS HEAT RATINGS

MODEL

MBH INPUT

MBH OUTPUT

WR180N/S24

300

240

WR180N/S32

400

320

WR240N/S24

300

240

WR240N/S32

400

320

WR300N/S24

300

240

WR300N/S32

400

320

For units with VFD and electric or gas heat, the
speed of the indoor blower motor continues to
be controlled by duct static pressure via the
VAV control board.

If there are VAV boxes present in the duct sys-
tem, the boxes must be driven to the full-open
position using a customer-supplied power
source to assure adequate airflow across elec-
tric heating elements or gas heat exchanger
tubes.

Advertising