23 blower motor and drive data, 24 static resistances, 25 power exhaust performance – York SUNLINE MAGNADRY WR 180 User Manual

Page 38

Advertising
background image

262292-YTG-B-0107

38

Unitary Products Group

TABLE 23: BLOWER MOTOR AND DRIVE DATA

MODEL

SIZE

DRIVE

BLOWER

RANGE

(RPM)

MOTOR

1

ADJUSTABLE MOTOR PULLEY

FIXED BLOWER PULLEY

BELT

(NOTCHED)

HP FRAME

EFF.

(%)

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

PITCH

LENGTH

(IN.)

QTY.

15 TON

Standard

790/970

5

184 T

89.5

1VP62

5.95

4.9-5.9

2

1-1/8

BK105

10.25

9.9

1

BX81

82.8

1

High

Speed

Access

940/1130 7.5

213 T

91

1-3/8

BK90

8.75

8.4

20 TON

Low

Speed

Drive

910/1100

7.5

213 T

91

1VP68

6.55

5.5-6.5

1-3/8

BK100

9.75

9.4

1-3/16

BX81

82.8

1

Standard

10

215 T

91

High

Speed

Access

1000/1180 15

254 T

91

1VP71

7.1

5.4-6.6

1-5/8

25 TON

Low

Speed

Drive

900/1100

7.5

213 T

91

1VP65

6.0

4.8-6.0

1-3/8

1B5V94

9.7

9.5

1-3/16

BX78

79.8

1

Standard

15

254 T

91

1-5/8

1-7/16

High

Speed

Access

1000/1200

1VP71

7.1

5.5-6.5

BX81

82.8

1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are

located in the moving air, upstream of any heating device.

2. Do NOT close this pully below 1 turn open.

TABLE 24: STATIC RESISTANCES

1

DESCRIPTION

RESISTANCE, IWG

CFM

15 TON

20 TON

25 TON

4500

6000

7500

6000

8000

9000

7500

8000

9000

WET INDOOR COIL

0.1

0.1

0.1

0.1

0.1

0.2

0.1

0.1

0.2

ELECTRIC HEAT OPTIONS

18 KW

0.3

0.4

0.4

0.4

0.4

0.5

0.4

0.4

0.5

36 KW

0.3

0.4

0.5

0.4

0.5

0.5

0.5

0.5

0.5

54 KW

0.4

0.5

0.5

0.5

0.5

0.6

0.5

0.5

0.6

72 KW

0.4

0.5

0.5

0.5

0.5

0.6

0.5

0.5

0.6

ECONOMIZER OPTION

0.1

0.1

0.1

0.1

0.1

0.2

0.1

0.1

0.2

HORIZONTAL DUCT CONNECTIONS

2

0.1

0.2

0.3

0.2

0.3

0.5

0.3

0.3

0.5

1. Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table.
2.

Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the
ESP values on the respective unit’s blower performance table.

TABLE 25: POWER EXHAUST PERFORMANCE

MOTOR

SPEED

1

STATIC RESISTANCE OF RETURN DUCTWORK, IWG

0.2

0.3

0.4

0.5

0.6

CFM

kW

CFM

kW

CFM

kW

CFM

kW

CFM

kW

HIGH

2

5250

0.83

4500

0.85

4200

0.88

3750

0.93

3000

0.99

MEDIUM

4900

0.77

3900

0.79

3500

0.82

2900

0.85

-

-

LOW

4400

0.72

3700

0.74

3000

0.78

-

-

-

-

1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.