7 cooling capacities for wr180 (alternate, Reheat mode) – York SUNLINE MAGNADRY WR 180 User Manual

Page 18

Advertising
background image

262292-YTG-B-0107

18

Unitary Products Group

TABLE 7: COOLING CAPACITIES FOR WR180 (ALTERNATE REHEAT MODE)

Air on Evaporator Coil

Temperature of Air on Condenser Coil

75°F

85°F

CFM

WB
(°F)

Total

Cap.

1

(MBH)

Total

2

Input

(kW)

Sensible Capacity (MBH)

*

Return Dry Bulb (°F)

Total

Cap.

1

(MBH)

Total

2

Input

(kW)

Sensible Capacity (MBH)

*

Return Dry Bulb (°F)

90

85

80

75

70

65

90

85

80

75

70

65

4500

67

88

10.6

23

21

19

16

14

11

80

11.2

18

16

14

12

10

9

62

79

10.1

44

42

39

37

35

32

72

10.8

35

34

32

30

28

26

57

70

9.9

48

46

44

41

39

36

66

10.6

39

37

35

34

32

30

5250

67

90

10.7

32

29

25

22

19

15

82

11.3

26

24

21

18

15

12

62

81

10.2

59

56

53

49

46

43

74

10.8

53

50

47

44

41

39

57

72

10.0

61

59

58

55

51

48

68

10.7

55

54

53

50

47

44

6000

67

92

10.8

40

36

32

28

23

19

85

11.3

35

31

27

24

20

16

62

82

10.3

73

70

66

61

57

53

76

10.9

70

66

62

58

55

51

57

73

10.0

73

73

72

68

64

60

70

10.7

70

70

70

66

62

58

6750

67

95

10.8

49

44

39

33

28

23

87

11.3

43

38

34

29

25

20

62

85

10.2

75

74

72

66

61

56

78

10.9

72

70

68

63

59

55

57

75

10.0

75

75

75

70

65

59

72

10.7

72

72

72

67

63

58

7500

67

98

10.7

58

52

46

39

33

27

90

11.3

51

45

40

34

29

24

62

88

10.2

78

78

78

71

65

59

81

10.9

74

74

74

68

63

58

57

78

10.0

78

78

78

72

65

59

74

10.7

74

74

74

68

63

58

95°F

105°F

4500

67

71

11.8

12

11

10

8

7

6

65

12.5

8

8

7

6

5

4

62

64

11.4

27

25

24

23

22

20

60

12.1

21

20

19

18

17

16

57

61

11.3

30

29

27

26

25

24

57

12.1

23

22

21

20

19

18

5250

67

74

11.8

21

19

16

14

12

10

69

12.6

16

15

13

11

9

8

62

68

11.5

46

44

41

39

37

35

63

12.2

41

40

38

36

34

33

57

64

11.4

48

48

47

45

43

40

60

12.1

43

42

42

40

38

36

6000

67

78

11.9

29

26

23

20

17

14

72

12.6

24

22

19

16

14

11

62

71

11.5

65

62

59

56

52

49

66

12.2

62

60

57

54

52

49

57

67

11.4

67

67

67

63

60

57

63

12.1

63

63

62

60

57

55

6750

67

79

11.9

36

32

29

25

21

17

73

12.6

31

28

24

21

18

15

62

72

11.5

67

66

64

60

57

53

66

12.2

63

62

61

57

54

51

57

68

11.4

68

68

68

64

60

57

64

12.1

64

64

63

60

57

54

7500

67

81

11.9

43

39

34

30

25

21

74

12.6

37

34

30

26

22

18

62

73

11.5

70

70

70

65

61

56

67

12.2

64

64

64

60

57

53

57

70

11.4

70

70

70

65

61

56

64

12.1

64

64

64

61

57

53

115°F

125°F

4500

67

60

13.3

5

4

4

3

3

2

54

14.0

-

-

-

-

-

-

62

55

12.8

15

14

14

13

13

12

50

13.5

9

9

9

8

8

8

57

53

12.8

16

15

15

14

14

13

50

13.5

9

8

8

8

8

8

5250

67

63

13.3

12

11

9

8

7

6

57

14.1

8

7

6

5

4

3

62

58

12.9

37

36

35

33

32

31

53

13.6

33

31

31

30

29

29

57

56

12.8

37

37

36

35

34

33

52

13.6

31

31

31

30

30

29

6000

67

66

13.4

19

17

15

13

11

9

60

14.1

14

13

11

9

8

6

62

60

12.9

59

57

55

53

51

49

55

13.6

55

54

53

52

50

49

57

59

12.9

59

59

58

56

54

52

54

13.6

54

54

54

53

51

50

6750

67

66

13.4

25

23

20

18

15

12

59

14.1

20

18

16

14

12

10

62

61

12.9

59

58

57

54

52

49

55

13.6

54

54

53

52

49

47

57

59

12.9

59

59

59

56

53

51

54

13.6

54

54

54

52

50

48

7500

67

66

13.4

32

28

25

22

19

16

59

14.1

26

23

21

18

16

13

62

61

12.9

59

59

59

56

53

49

55

13.6

54

54

54

51

48

46

57

59

12.9

59

59

59

56

53

50

54

13.6

54

54

54

52

49

46

1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower

Performance table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

All Sensible Capacity