26 wr electrical data - standard drive, Motor w/o powered conv. outlet – York SUNLINE MAGNADRY WR 180 User Manual

Page 39

Advertising
background image

262292-YTG-B-0107

Unitary Products Group

39

NOTE 1: HACR Type per NEC.

TABLE 26: WR ELECTRICAL DATA - STANDARD DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET

MODEL

(TONNAGE)

VOLTAGE

COMPRESSORS

OD FAN

MOTORS

FLA EACH

ID

BLOWER

MOTOR

FLA

CONV

OUTLET

AMPS

HEATER OPTION

MIN.

CIRCUIT

AMPACITY

(AMPS)

MAX. FUSE/

BRKR

1

SIZE

(AMPS)

RLA

EACH

LRA

EACH

MODEL

KW

STAGES

AMPS

180

(15)

208

22.4

164

2.1

17.7

0.0

None

-

-

-

76.5

90

E18

13.5

1

37.5

76.5

90

E36

27

2

74.9

115.8

125

E54

40.6

2

112.7

163.0

175

E72

54.1

2

150.2

172.3

200

230

22.4

164

2.1

16.4

0.0

None

-

-

-

75.2

90

E18

18.0

1

43.3

75.2

90

E36

36.0

2

86.6

128.8

150

E54

54.0

2

129.9

150.4

175

E72

72.0

2

173.2

193.7

225

460

10.9

100

1.2

8.2

0.0

None

-

-

-

37.5

45

E18

18.0

1

21.7

37.5

45

E36

36.0

2

43.3

64.4

70

E54

54.0

2

65.0

75.2

90

E72

72.0

2

86.6

96.9

110

575

8.3

78

0.9

6.6

0.0

None

-

-

-

28.9

35

E18

18.0

1

17.3

29.9

35

E36

36.0

2

34.6

51.6

60

E54

54.0

2

52.0

60.2

70

E72

72.0

2

69.3

77.5

90

240

(20)

208

30.1

225

2.4

24.2

0.0

None

-

-

-

101.5

125

E18

13.5

1

37.5

101.5

125

E36

27

2

74.9

123.9

125

E54

40.6

2

112.7

171.1

175

E72

54.1

2

150.2

180.4

200

230

30.1

225

2.4

24.2

0.0

None

-

-

-

101.5

125

E18

18.0

1

43.3

101.5

125

E36

36.0

2

86.6

138.5

150

E54

54.0

2

129.9

160.2

175

E72

72.0

2

173.2

203.5

225

460

15.5

114

0.9

12.1

0.0

None

-

-

-

50.6

60

E18

18.0

1

21.7

50.6

60

E36

36.0

2

43.3

69.3

70

E54

54.0

2

65.0

80.1

90

E72

72.0

2

86.6

101.7

110

575

12.1

80

0.6

10.3

0.0

None

-

-

-

39.9

50

E18

18.0

1

17.3

39.9

50

E36

36.0

2

34.6

56.2

60

E54

54.0

2

52.0

64.8

70

E72

72.0

2

69.3

82.2

90

300

(25)

208

42.3

245

2.4

38.6

0.0

None

-

-

-

143.4

175

E18

13.5

1

37.5

143.4

175

E36

27

2

74.9

143.4

175

E54

40.6

2

112.7

189.1

200

E72

54.1

2

150.2

198.4

225

230

42.3

245

2.4

38.6

0.0

None

-

-

-

143.4

175

E18

18.0

1

43.3

143.4

175

E36

36.0

2

86.6

156.5

175

E54

54.0

2

129.9

178.2

200

E72

72.0

2

173.2

221.5

250

460

17.6

125

0.9

19.3

0.0

None

-

-

-

62.9

80

E18

18.0

1

21.7

62.9

80

E36

36.0

2

43.3

78.3

80

E54

54.0

2

65.0

89.1

100

E72

72.0

2

86.6

110.7

125

575

14.5

100

0.6

16.2

0.0

None

-

-

-

51.7

60

E18

18.0

1

17.3

51.7

60

E36

36.0

2

34.6

63.6

70

E54

54.0

2

52.0

72.2

80

E72

72.0

2

69.3

89.5

100

VOLTAGE LIMITATIONS

ELECTRIC HEAT CORRECTION FACTORS

POWER SUPPLY

VOLTAGE

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTIPLIER

MIN.

MAX.

208

208

1.00

VOLTAGE

LIMITATIONS

1

208/230-3-60

187

253

240

230

0.92

460-3-60

414

506

480

460

0.92

575-3-60

518

630

600

575

0.92

1.

Utilization Range “A” in accordance with ARI Standard 110.