Hot water heating, Physical data hot water coil - 1 row, Table 9: water pressure drop (1 row, 25 & 30 ton) – York Y33 User Manual

Page 14: Table 11: hot water coil (1 row, 25 & 30 ton), Piping connections, Water pressure drop (1 row, 25 & 30 ton), 10 static resistance hot water coil, 25 & 30 ton), 11 hot water coil (1 row, 25 & 30 ton)

Advertising
background image

246653-YTG-E-0108

14

Johnson Controls Unitary Products

HOT WATER HEATING

1

The YORK Millennium Rooftop units (30 - 40 Ton sizes) can
be furnished with a YORK hot water coil as the source of heat
(Bottom Supply Only). A one or two row coil will be factory
installed in the heating section downstream of the supply air
fan and just above the supply air opening in the bottom of the
unit.

The hot water control valve will not be provided. The installer
will need to field supply a water valve. The installer must also
connect the hot water piping, and valve wiring at the job site
for the hot water heat section to be operational.

For all hot water coils the entering water temperature should
not exceed 200°F.

PHYSICAL DATA HOT WATER COIL - 1 ROW

Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel

Coil Construction. . . . . . . . . . . . . . . . Al Fin / Cu. Tube

Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . .006”

Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .016”

Tubes / Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Fins Per Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.50”

Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”

Face Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.16ft.

2

Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71lbs.

Operating Weight . . . . . . . . . . . . . . . . . . . . . . . .83lbs.

NOTE: Water pressure drop numbers are based on 60°F

entering air temperature, 2.00” maximum air pres-
sure drop across the hot water coil(s). ARI certified
ratings at covering other conditions are available
upon request. Hot water coils are approved for use
with glycol (rates available upon request).

PIPING CONNECTIONS

The hot water piping must enter the unit through the floor of
the heat section compartment. The access doors to the com-
partment are gasketed so the compartment can be sealed.
However, as added protection for water leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic (see the following illustration for approximate
location of the compartment and piping connections.

1. Hot water, steam or electric heat is not available for

front or rear supply.

TABLE 9: WATER PRESSURE DROP (1 ROW, 25 &

30 TON)

GPM

10

20

30

40

W

ATER

P

RESSURE

D

ROP

0.9

3.0

6.0

10.0

TABLE 10: STATIC RESISTANCE HOT WATER COIL

(25 & 30 TON)

CFM 6000

8000

10000

15000

A

IR

P

RESSURE

D

ROP

1 R

OW

0.07

0.11

0.16

0.32

A

IR

P

RESSURE

D

ROP

2 R

OW

0.14

0.23

0.33

0.65

DO NOT use tin based solder. Brazing with tin
based solder could cause equipment damage or
possible injury to OCCUPANTS of the structure
that is being conditioned.

TABLE 11: HOT WATER COIL (1 ROW, 25 & 30

TON)

1

1.

Based on 60°F entering air temperature, 2.00” maximum pres-
sure drop across the hot water coil.

GPM

CFM

C

APACITY

(MBH)

AT

E

NTERING

W

ATER

T

EMPERATURE

140 °F

160 °F

180 °F

200 °F

10

6000

91.4

115.3

139.3

163.6

8000

102

128.8

155.8

182.9

10000

110.4

139.5

168.8

198.4

12000

117.3

148.4

179.6

211.2

15000

125.9

159.2

192.9

226.9

20

6000

103

129.4

156

182.7

8000

116.8

147

177.2

207.7

10000

128.2

161.3

194.7

228.2

12000

137.8

173.6

209.5

245.6

15000

150

189

228.2

267.8

30

6000

107.6

135

162.5

190.1

8000

122.8

154.3

185.8

217.5

10000

135.5

170.3

205.1

240.2

12000

146.4

184

221.8

259.7

15000

160.3

201.6

243

284.8

40

6000

110.1

138

166

194.1

8000

126.1

158.2

190.5

222.8

10000

139.6

175.2

210.9

246.8

12000

151.2

189.8

228.5

267.5

15000

166.1

208.6

251.3

294.1