Figure 1 - hot water piping cross-section, Table 13: hot water coil (1 row 40 ton), Hot water piping cross-section – York Y33 User Manual

Page 15: 12 static resistance hot water coil, 1 row, 40 ton), 13 hot water coil (1 row 40 ton)

Advertising
background image

246653-YTG-E-0108

Johnson Controls Unitary Products

15

FIGURE 1 - HOT WATER PIPING CROSS-SEC-

TION

TABLE 12: STATIC RESISTANCE HOT WATER COIL

(1 ROW, 40 TON)

CFM

8000

11000

14000

20000

A

IR

P

RESSURE

D

ROP

1 R

OW

0.11

0.19

0.29

0.52

A

IR

P

RESSURE

D

ROP

2 R

OW

0.23

0.39

0.58

1.06

HOT WATER

COIL

CONDENSING

SECTION

INLET (2")

OUTLET (2")

CL

2.55"

8.38"

2.25"

11.88"

26"

15.8"

88.75"

HEAT SECTION

COMPARTMENT

(1 OR 2 ROW)

OUTSIDE OF

BASE RAIL

TABLE 13: HOT WATER COIL (1 ROW 40 TON)

1

1.

Based on 60°F entering air temperature, 2.00” maximum pres-
sure drop across the hot water coil.

GPM

CFM

C

APACITY

(MBH)

AT

E

NTERING

W

ATER

T

EMPERATURE

140 °F

160 °F

180 °F

200 °F

10

8000

102

128.8

155.8

182.9

11000

114

144.1

174.4

205.1

14000

123.2

155.9

188.8

222.1

17000

130.6

165.4

200.4

235.8

20000

136.8

173.3

210.1

247.3

20

8000

116.8

147

177.2

207.7

11000

133.2

167.7

202.3

237.2

14000

146.2

184.2

222.4

260.8

17000

157

197.9

239

280.5

20000

166.2

209.6

253.2

297.3

30

8000

122.8

154.3

185.8

217.5

11000

141.2

177.4

213.8

250.3

14000

155.9

196.1

236.4

276.9

17000

168.3

211.8

255.4

299.3

20000

179.1

225.3

271.8

318.6

40

8000

126.1

158.2

190.5

222.8

11000

145.6

182.7

220

257.5

14000

161.4

202.6

244.1

285.8

17000

174.7

219.5

264.5

309.7

20000

186.3

234.2

282.3

330.6

Advertising
This manual is related to the following products:

Y34, Y32