38 fan performance - 30 ton, Table 38: fan performance - 30 ton – York Y33 User Manual

Page 48

Advertising
background image

246653-YTG-E-0108

48

Johnson Controls Unitary Products

4. Shaded RPMs require Class II blower.

TABLE 38: FAN PERFORMANCE - 30 TON

1,

2

A

IRFLOW

(CFM)

A

VAILABLE

E

XTERNAL

S

TATIC

P

RESSURE

(IWG)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

6000

321

0.9

373

1.2

422

1.6

469

1.9

513

2.2

7000

357

1.4

404

1.7

447

2.0

490

2.3

529

2.7

8000

398

1.9

437

2.2

477

2.6

515

3.0

551

3.5

9000

436

2.6

473

2.9

509

3.4

543

3.8

577

4.2

10000

477

3.4

511

3.9

543

4.3

575

4.7

606

5.3

11000

519

4.4

549

4.9

579

5.4

609

5.9

637

6.4

12000

560

5.7

589

6.2

617

6.7

643

7.2

670

7.8

13000

603

7.1

629

7.7

654

8.2

680

8.8

705

9.3

14000

645

8.8

669

9.3

694

10.0

718

10.5

741

11.2

15000

688

10.7

711

11.3

733

12.1

755.6

12.7

778

13.3

A

IRFLOW

(CFM)

A

VAILABLE

E

XTERNAL

S

TATIC

P

RESSURE

(IWG)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

6000

554

2.5

596

2.9

632

3.4

668

3.7

703

4.1

7000

568

3.2

607

3.6

642

4.0

676

4.4

710

4.8

8000

587

3.9

622

4.3

655

4.7

689

5.3

720

5.7

9000

610

4.7

642

5.1

673

5.7

704

6.2

734

6.7

10000

636

5.8

666

6.3

695

6.8

723

7.4

751

7.9

11000

665

6.9

693

7.5

720

8.0

746

8.6

773

9.2

12000

697

8.3

722

8.9

747

9.6

772

10.1

797

10.7

13000

729

10.0

753

10.5

777

11.2

801

11.9

824

12.5

14000

764

11.9

787

12.5

809

13.2

831

13.9

853

14.5

15000

800

14.0

821

14.6

842

15.3

863

16.0

884

16.7

A

IRFLOW

(CFM)

A

VAILABLE

E

XTERNAL

S

TATIC

P

RESSURE

(IWG)

2.2

2.4

2.6

2.8

3.0

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

6000

734

4.5

765

4.9

796

5.4

824

5.8

850

6.3

7000

741

5.3

772

5.8

803

6.3

830

6.7

858

7.2

8000

750

6.2

781

6.7

810

7.2

837

7.8

865

8.3

9000

763

7.2

792

7.8

820

8.3

847

8.9

873

9.5

10000

779

8.4

807

9.0

833

9.6

859

10.2

885

10.8

11000

799

9.8

824

10.4

849

11.0

874

11.7

899

12.3

12000

821

11.3

845

12.1

869

12.7

893

13.3

916

14.1

13000

847

13.2

869

13.9

892

14.6

914

15.2

936

15.9

14000

874

15.2

896

15.9

917

16.6

938

17.3

959

18.1

15000

904

17.4

924

18.3

944

19.0

964

19.7

984

20.5

A

IRFLOW

(CFM)

A

VAILABLE

E

XTERNAL

S

TATIC

P

RESSURE

(IWG)

3.2

3.4

3.6

3.8

4.0

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

6000

877

6.7

904

7.1

928

7.7

951

8.1

975

8.6

7000

885

7.7

911

8.2

935

8.7

959

9.2

984

9.7

8000

892

8.8

917

9.3

942

9.9

966

10.4

991

10.9

9000

900

10.0

925

10.6

949

11.1

974

11.8

998

12.4

10000

910

11.4

934

12.1

958

12.7

982

13.3

1006

14.0

11000

923

13.0

946

13.7

970

14.3

993

14.9

1015

15.5

12000

939

14.7

961

15.3

984

16.1

1006

16.8

1028

17.5

13000

958

16.6

980

17.3

1001

18.1

1022

18.8

1043

19.5

14000

980

18.8

1001

19.6

1021

20.4

1040

21.1

1060

21.8

15000

1004

21.2

1023

22.1

1043

22.9

1062

23.6

1081

24.5

1.

Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.

2.

Refer to Tables 10, 15, 21 and 42 for component additions and deductions to fan performance tables.

3.

BHP includes drive losses.

Advertising
This manual is related to the following products: