Table 11: electrical data 10 ton – York DM150 User Manual

Page 19

Advertising
background image

127408-YIM-B-0606

Unitary Products Group

19

TABLE 10: ELECTRICAL DATA 7-1/2 TON

Voltage

*

Compressors

OD

Fan

Motors

Supply
Blower

Motor FLA

Pwr Exh

Motor

Electric

Heater

Model No.

Actual

kW

Heater

Amps

Min. Circuit

Ampacity

(Amps)

MCA

w/Power

Exhaust

(Amps)

Max Fuse

Size (Amps)

Max Fuse Size

w/Power

Exhaust

(Amps)

RLA

ea.

LRA

ea.

FLA

ea.

3 HP

FLA

3 HP

2 HP

3 HP

2 HP

380

8.3

62

1.1

4.9

2.2

None

-

-

26.1

28.3

30

35

415

8.3

62

1.1

4.9

2.2

None

-

-

26.1

28.3

30

35

*.

Unit voltage limitations: minimum utilization 342 volts, maximum utilization 457 volts.

†.

Maximum HACR breaker of the same amp size is acceptable.

TABLE 11: ELECTRICAL DATA 10 TON

Voltage

*

Compressors

OD

Fan

Motors

Supply Blower

Motor FLA

Pwr Exh

Motor

Electric

Heater

Model No.

Actual

kW

Heater

Amps

Min. Circuit

Ampacity

(Amps)

MCA

w/Power

Exhaust

(Amps)

Max Fuse

Size (Amps)

Max Fuse Size

w/Power

Exhaust

(Amps)

RLA

ea.

LRA

ea.

FLA

ea.

2 HP

(1.5 kW)

4 HP

(3 kW)

FLA

2 HP

(1.5 kW)

4 HP

(3 kW)

2 HP

(1.5

kW)

4 HP

(3 kW)

2 HP

(1.5 kW)

4 HP

(3 kW)

2 HP

(1.5

kW)

4 HP

(3

kW)

380

9.6

80

1.1

5.2

7.5

2.2

None

-

-

29.0

31.3

31.2

33.5

35

40

40

40

2TP04521850

11.3

17.2

29.0

31.3

31.2

33.5

35

40

40

40

2TP04522450

15.0

22.8

35.0

37.9

37.7

40.6

35

40

40

45

2TP04523650

21.3

32.4

47.0

49.8

49.7

52.6

50

50

50

60

2TP04525450

33.8

51.4

70.7

73.6

73.4

76.3

80

80

80

80

415

9.6

80

1.1

5.2

7.5

2.2

None

-

-

29.0

31.3

31.2

33.5

35

40

40

40

2TP04521850

13.5

18.8

30.0

32.9

32.7

35.6

35

40

40

40

2TP04522450

17.9

24.9

37.6

40.5

40.4

43.3

40

45

45

45

2TP04523650

25.4

35.3

50.7

53.5

53.4

56.3

60

60

60

60

2TP04525450

40.4

56.2

76.8

79.6

79.5

82.4

80

80

80

90

*.

Unit voltage limitations: minimum utilization 342 volts, maximum utilization 457 volts.

†.

Maximum HACR breaker of the same amp size is acceptable.