FIGURE 30: UNIT CONTROL BOARD

TABLE 53: IGNITION CONTROL FLASH CODES

FLASHES

FAULT CONDITIONS

CHECK

STEADY ON

Control Failure

Control

HEARTBEAT

Normal Operation

1

Not Applicable

2

Pressure Switch
Stuck Closed

Pressure Switch

3

Pressure Switch Failed
To Close

Venter Pressure Switch
Vent Blocked

4

Limit Switch Open

Main Limit
AUX Limit

5

Flame Present With Gas
Off First Stage Gas Valve
Energized With W1 Off
Second Stage Gas Valve
Energized With First
Stage
Gas Valve Off

Gas Valve

6

Ignition Lockout

Gas Flow
Gas Pressure
Gas Valve
Flame Sensor

STEADY OFF

No Power Or Control
Failure

24VAC or Control

Check

Alarm

History

Reset All

ASCDs for
One Cycle

Non Alarm

Condition Green

LED Flashing

Current Alarm

Flashed

Red LED