Caution: equipment damage – Xantrex Technology Inverter Communications Adapter User Manual

Page 26

Advertising
background image

Installation

10

975-0052-01-01 Rev A

Positive Ground or PV Ground Fault Protection
Installations

When using the ICA in inverter installations that have DC
ground fault protection (PVGFP-CF) or where the inverter is
connected in a “positive ground” configuration, an opto-
isolator must be connected somewhere between the ICA and
the computer com port. Opto-isolators can be obtained
through www.blackbox.com (part SP400A-R3 and PS576 -
9 Vdc power supply).

CAUTION: Equipment Damage

Damage to the inverter and ICA can occur if an opto-isolator is not
used in a “positive ground” configuration or in installations that
have DC ground fault protection.

Advertising