INSTALLATION

The Automatic Generator Start Control System (AGS) consists of
two modules, the Remote Panel and the Controller.

Service Precaution Labels

Install service precaution labels on or near the generator and near
the AGS Remote.

AGS Remote Panel

This AGS Remote Panel provides information and control of the
Control Module. Power for this Remote Panel comes from the
Control Module. The Remote Panel comes on automatically when
power is applied to the AGS Control Module.

The AGS Remote Panel measures 5.75'' (W) X 3.75'' (H) X 0.65''
(D). Use the supplied template to cut the proper size hole. Mount
the Remote Panel unit using the screws supplied.

Route the control cable from the AGS Remote Panel to the Con-
trol Module. Connect the control cable to the AGS Remote Panel
and Control Module using the data connectors on the supplied
cable.

Power Up Indications

When power is first applied to the AGS Remote, the AGS Remote
establishes communications with the Controller. It can take up to
four seconds to establish communications.

AGS Controller

The AGS Controller may be mounted in any convenient location.
Mount the AGS Controller using the screws supplied. The AGS
Controller may be mounted up to 250 feet from the AGS Remote.