Table 1: physical data – York PREDATOR DM150 User Manual

Page 12

Advertising
background image

036-21044-003-A-0304

12

Unitary Products

TABLE 1: PHYSICAL DATA

Component

Models

090

120

150

Evaporator

Blower

Blower, Centrifugal

Dia. X Wd. in.

(Dia. X Wd. mm.)

15 x 15

(381 x 381)

15 x 15

(381 x 381)

15 x 15

(381 x 381)

Motor, Standard - HP (kW)

1-1/2 (1.1)

2 (1.5)

4 (3)

Motor, Optional - HP (kW)

2 (1.5)

4 (3)

N/A

Evaporator

Coil

Rows

2

3

4

Fins per 2.54 cm (1 in.)

15

15

15

Height - in. (mm.)

32 (810)

40 (1020)

40 (1020)

Face Area - ft.

2

(m

2

)

10.6 (0.98)

13.2 (1.23)

13.2 (1.23)

Condenser

Fan

(2 per Unit)

Propeller Dia. - in. (mm.) ea.

24 (610)

24 (610)

24 (610)

Motor - HP (kW) ea.

1/3 (0.25)

3/4 (0.56)

3/4 (0.56)

Airflow - CFM (m

3

/s) ea.

3700 (1.75)

3700 (1.75)

3700 (1.75)

Condenser

Coil

(2 per unit)

Rows (each)

1

1

2

Fins per inch (2.54 mm)

20

20

20

Height - in. (mm.)

28 (711)

44 (1120)

44 (1120)

Face Area - ft.

2

(m

2

)

9.2 (.86)

14.5 (1.35)

14.5 (1.35)

Refrigerant

Charge

System 1 - lbs. (kg.)

4.38 (1.99)

6.75 (3.06)

11.0 (4.99)

System 2 - lbs. (kg.)

4.13 (1.87)

6.13 (2.78)

10.0 (4.54)

Compressors

Quantity

2

2

2

Type

Recip

Recip

Scroll

Air Filters

Size

Wd. x Ht. x Thickness in.

(Wd. x Ht. x Thickness mm.)

25 x 20 x 2

(635 x 508 x 51)

25 x 20 x 2

(635 x 508 x 51)

25 x 20 x 2

(635 x 508 x 51)

Number Per Unit

4

4

4

Advertising