Table 9: cooling capacity 43.9 kw unit - metric – York PREDATOR DM150 User Manual

Page 19

Advertising
background image

036-21044-003-A-0304

Unitary Products

19

TABLE 9: COOLING CAPACITY 43.9 KW UNIT - METRIC

Air On

Evap. Coil

Temperature of Air on Condenser Coil 29°C

Temperature of Air on Condenser Coil 35°C

m

3

/s

WB

(°C)

Tot.

Cap.

1

(kW)

Tot.

Input

2

(kW)

Sensible Capacity (kW)

1

Return Dry Bulb (°C)

Tot.

Cap.

1

(kW)

Tot.

Input

2

(kW)

Sensible Capacity (kW)

1

Return Dry Bulb (°C)

30

28

27

25

23

22

20

30

28

27

25

23

22

20

1.77

22

44

11.8

26

23

20

17

14

-

-

42

13.0

26

23

20

16

13

-

-

19

41

11.5

34

31

27

24

21

18

15

39

12.6

33

30

26

23

20

17

14

17

36

11.2

36

34

31

28

25

21

18

34

12.4

34

33

30

27

24

20

17

14

35

11.3

35

34

31

28

25

21

18

33

12.5

33

33

29

26

23

20

17

2.06

22

46

11.8

29

26

22

18

15

-

-

43

13.0

29

25

21

18

14

-

-

19

42

11.5

37

34

30

26

23

19

15

40

12.5

36

33

29

25

21

18

14

17

37

11.2

37

36

34

30

26

23

19

35

12.4

35

35

33

29

25

22

18

14

36

11.3

36

36

34

30

26

23

19

34

12.4

34

34

32

28

25

21

17

2.36

22

47

11.8

33

28

24

20

15

-

-

45

12.9

32

28

23

19

15

-

-

19

44

11.5

41

37

33

28

24

20

15

42

12.5

40

36

31

27

23

19

14

17

39

11.3

39

39

37

32

28

24

20

37

12.3

37

37

35

31

27

23

18

14

37

11.3

37

37

37

32

28

24

20

35

12.4

35

35

35

31

26

22

18

2.65

22

48

11.9

39

34

29

24

19

-

-

46

13.1

38

33

28

23

18

-

-

19

45

11.6

44

41

39

34

30

25

20

43

12.6

42

40

38

33

28

23

18

17

39

11.3

39

39

39

34

29

24

19

38

12.5

38

38

37

32

27

22

18

14

38

11.4

38

38

38

33

28

23

18

36

12.5

36

36

36

31

26

21

16

2.95

22

49

11.9

45

39

34

28

23

-

-

47

13.2

44

38

33

27

22

-

-

19

46

11.6

46

46

46

41

35

30

24

44

12.8

44

44

44

38

33

27

22

17

40

11.4

40

40

40

35

30

24

19

39

12.6

39

39

39

33

28

22

17

14

39

11.4

39

39

39

33

28

22

17

37

12.7

37

37

37

31

26

21

15

Temperature of Air on Condenser Coil 41°C

Temperature of Air on Condenser Coil 46°C

1.77

22

39

14.3

25

22

19

16

13

-

-

37

15.6

24

21

18

15

12

-

-

19

36

13.8

32

29

25

22

19

16

13

34

15.1

31

28

24

21

18

15

12

17

32

13.6

32

32

28

25

22

19

16

30

14.9

30

30

27

24

21

18

14

14

31

13.8

31

31

28

25

21

18

15

29

15.0

29

29

26

23

20

17

13

2.06

22

41

14.3

28

24

21

17

13

-

-

38

15.6

27

23

20

16

12

-

-

19

38

13.8

35

32

28

24

20

17

13

35

15.1

34

30

27

23

19

16

12

17

33

13.6

33

33

31

27

24

20

16

31

14.9

31

31

30

26

22

18

15

14

32

13.7

32

32

30

27

23

19

15

30

15.0

30

30

28

25

21

17

14

2.36

22

42

14.3

31

27

22

18

14

-

-

40

15.6

30

26

21

17

13

-

-

19

39

13.8

38

35

30

26

22

17

13

36

15.1

36

33

29

25

21

16

12

17

34

13.6

34

34

34

30

25

21

17

32

14.9

32

32

32

28

24

19

15

14

33

13.7

33

33

33

29

24

20

16

31

15.0

31

31

31

27

22

18

14

2.65

22

43

14.4

36

31

26

21

16

-

-

40

15.7

33

29

24

19

14

-

-

19

40

13.9

40

38

35

30

25

20

15

37

15.2

37

36

32

27

22

18

13

17

35

13.7

35

35

35

30

25

20

15

33

15.0

33

33

33

28

23

18

13

14

34

13.8

34

34

34

29

24

19

14

32

15.1

32

32

32

27

22

17

12

2.95

22

44

14.5

40

35

29

24

18

-

-

41

15.8

37

32

26

21

15

-

-

19

41

14.0

41

41

40

34

29

23

18

38

15.3

38

38

35

30

24

19

13

17

36

13.8

36

36

36

31

25

20

14

34

15.0

34

34

34

28

23

17

12

14

35

13.9

35

35

35

29

24

18

13

32

15.2

32

32

32

27

21

16

10

Temperature of Air on Condenser Coil 52°C

1.77

22

35

16.9

24

20

17

14

11

-

-

19

32

16.4

30

27

23

20

17

14

11

17

28

16.1

28

28

26

22

19

16

13

14

27

16.3

27

27

24

21

18

15

12

2.06

22

36

16.9

26

23

19

15

11

-

-

19

33

16.4

32

29

26

22

18

15

11

17

29

16.1

29

29

28

24

21

17

13

14

28

16.3

28

28

27

23

19

16

12

2.36

22

37

16.9

29

25

21

16

12

-

-

19

34

16.4

34

32

28

24

19

15

11

17

30

16.1

30

30

30

26

22

18

13

14

29

16.3

29

29

29

25

20

16

12

2.65

22

37

17.0

31

27

22

17

12

-

-

19

34

16.5

34

34

29

25

20

15

10

17

31

16.2

31

31

31

26

21

16

11

14

29

16.4

29

29

29

25

20

15

10

2.95

22

38

17.1

34

28

23

17

12

-

-

19

35

16.5

35

35

31

26

20

15

9

17

31

16.3

31

31

31

26

20

15

9

14

30

16.5

30

30

30

24

19

14

8

1 These capacities are gross ratings. For net

capacity, deduct air blower motor, MBh = 3.415
x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air
blower motor.

2 These ratings include condenser fan motors

and the compressor motors but not the supply
air blower motor.

Advertising