Table 6: cooling capacity 10 ton unit - imperial – York PREDATOR DM150 User Manual

Page 16

Advertising
background image

036-21044-003-A-0304

16

Unitary Products

TABLE 6: COOLING CAPACITY 10 TON UNIT - IMPERIAL

Air On

Evap. Coil

Temperature of Air on Condenser Coil 85°F

Temperature of Air on Condenser Coil 95°F

CFM

WB
(°F)

Tot.

Cap.

1

(MBH)

Tot.

Input

2

(kW)

Sensible Capacity (MBH)

1

Return Dry Bulb (°F)

Tot.

Cap.

1

(MBH)

Tot.

Input

2

(kW)

Sensible Capacity (MBH)

1

Return Dry Bulb (°F)

86

83

80

77

74

71

68

86

83

80

77

74

71

68

3000

72

148

11.2

82

73

65

56

48

-

-

137

12.0

79

71

62

54

45

-

-

67

134

10.8

102

94

85

77

68

60

51

124

11.6

98

90

81

73

64

56

47

62

125

10.5

121

112

103

95

86

78

69

115

11.2

115

110

101

93

84

75

67

57

123

10.6

123

116

107

99

90

82

73

110

11.4

110

110

101

93

84

76

67

3500

72

149

11.4

89

79

69

59

49

-

-

139

12.2

86

76

66

56

46

-

-

67

136

11.0

111

101

91

81

71

61

51

126

11.7

106

96

86

76

66

56

46

62

126

10.6

124

120

110

100

90

80

70

117

11.4

117

114

107

97

87

77

67

57

124

10.7

124

120

114

104

94

84

74

112

11.5

112

112

107

97

87

77

67

4000

72

150

11.6

97

85

74

62

50

-

-

141

12.4

93

82

70

58

47

-

-

67

137

11.2

120

108

97

85

73

62

50

128

11.9

115

103

91

80

68

56

45

62

127

10.8

127

127

117

106

94

82

71

119

11.5

119

119

113

102

90

78

67

57

125

10.9

125

125

122

110

98

87

75

113

11.7

113

113

113

102

90

78

67

4500

72

153

11.7

105

92

78

65

52

-

-

143

12.4

103

90

76

63

50

-

-

67

139

11.3

130

116

103

90

76

63

50

129

12.0

122

113

100

86

73

60

47

62

130

10.9

130

130

125

111

98

85

72

120

11.6

120

120

117

104

91

78

64

57

127

11.0

127

127

125

112

99

86

72

115

11.7

115

115

115

101

88

75

61

5000

72

156

11.7

113

98

83

68

53

-

-

144

12.5

113

98

83

68

53

-

-

67

141

11.4

139

124

109

94

79

65

50

130

12.1

130

123

108

93

79

64

49

62

132

11.0

132

132

132

117

102

87

72

122

11.7

122

122

122

107

92

77

62

57

129

11.1

129

129

129

114

100

85

70

116

11.8

116

116

116

101

86

71

56

Temperature of Air on Condenser Coil 105°F

Temperature of Air on Condenser Coil 115°F

3000

72

129

12.8

75

67

58

50

41

-

-

122

13.5

71

63

54

46

37

-

-

67

114

12.3

94

86

77

68

60

51

43

105

13.0

90

81

73

64

56

47

38

62

109

11.9

109

103

95

86

78

69

61

102

12.6

102

97

89

80

72

63

55

57

104

12.1

104

102

93

84

76

67

59

98

12.8

98

93

85

76

68

59

51

3500

72

130

13.0

82

72

62

52

42

-

-

122

13.7

78

68

58

48

38

-

-

67

115

12.5

102

92

82

72

62

52

42

105

13.2

97

88

78

68

58

48

38

62

110

12.1

110

107

101

91

81

71

61

102

12.8

102

100

95

85

75

65

55

57

105

12.3

105

103

99

89

79

69

59

97

13.0

97

95

91

81

71

61

51

4000

72

131

13.1

89

78

66

54

43

-

-

121

13.9

85

74

62

51

39

-

-

67

116

12.7

110

99

87

76

64

52

41

105

13.4

105

95

83

72

60

48

37

62

111

12.3

111

111

108

96

84

73

61

102

13.0

102

102

102

90

79

67

55

57

105

12.4

105

105

105

94

82

70

59

97

13.2

97

97

97

86

74

62

51

4500

72

133

13.2

98

85

72

58

45

-

-

124

14.0

94

80

67

54

40

-

-

67

118

12.7

115

108

95

82

68

55

42

107

13.5

107

102

90

77

63

50

37

62

112

12.4

112

112

111

98

84

71

58

104

13.1

104

104

104

91

78

64

51

57

107

12.5

107

107

107

94

80

67

54

99

13.3

99

99

99

86

73

60

46

5000

72

135

13.3

107

92

77

63

48

-

-

127

14.1

102

87

72

57

42

-

-

67

120

12.8

120

116

102

87

73

58

43

110

13.6

110

110

96

82

67

52

37

62

114

12.5

114

114

114

99

84

69

54

106

13.2

106

106

106

92

77

62

47

57

109

12.6

109

109

109

94

79

64

49

102

13.4

102

102

102

87

72

57

42

Temperature of Air on Condenser Coil 125°F

3000

72

115

14.2

67

59

50

42

33

-

-

67

96

13.7

85

77

68

60

51

43

34

62

96

13.3

96

91

83

74

66

57

48

57

92

13.5

92

85

77

68

59

51

42

3500

72

113

14.5

74

64

54

44

34

-

-

67

95

13.9

93

84

74

64

54

44

33

62

95

13.5

95

92

89

79

69

59

49

57

90

13.8

90

87

83

73

63

53

42

4000

72

112

14.7

82

70

58

47

35

-

-

67

94

14.2

94

91

79

68

56

44

33

62

93

13.8

93

93

93

84

73

61

49

57

89

14.0

89

89

89

77

66

54

43

4500

72

115

14.8

89

76

62

49

36

-

-

67

96

14.3

96

96

85

72

58

45

32

62

96

13.8

96

96

96

84

71

58

44

57

92

14.1

92

92

92

79

65

52

39

5000

72

118

14.9

96

81

66

51

37

-

-

67

99

14.4

99

99

90

76

61

46

31

62

99

13.9

99

99

99

84

69

54

39

57

95

14.2

95

95

95

80

65

50

35

1 These capacities are gross ratings. For net

capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.

2 These ratings include condenser fan motors

and the compressor motors but not the supply
air blower motor.

Advertising
This manual is related to the following products: