Table 2: capacity ratings imperial, Table 3: capacity ratings metric – York PREDATOR DM150 User Manual

Page 13

Advertising
background image

036-21044-003-A-0304

Unitary Products

13

TABLE 2: CAPACITY RATINGS IMPERIAL

Model

Cooling Capacity

Sound
Rating

(dB)

Nominal

Electric

Heat

Capacity

(kW)

1

Gas Heat Capacity

(80 / 67-95°F)

Input

(MBH)

Output
(MBH)

Temp

Rise (°F)

Gas Line

Size

(in. OD)

Cooling Cap. (MBH)

Options

MBH

EER

090

DM

89

9.00

87

7, 14,

18, 27

-

-

-

-

10

-

-

-

-

120

96

15-45

3/4

15

-

-

-

-

180

144

30-60

3/4

120

DM

116

9.0

85

14, 18,

27, 41

-

-

-

-

15

-

-

-

-

180

144

20-50

3/4

150

DM

138

9.0

84

14, 18,

27, 41

-

-

-

-

15

-

-

-

-

180

144

10-40

3/4

1. Electric heaters rated at 415V. See tables 10 through 12 for kW ratings at 380V.

TABLE 3: CAPACITY RATINGS METRIC

Model

Cooling Capacity

Sound
Rating

(dB)

Nominal

Electric

Heat

Capacity

(kW)

1

Gas Heat Capacity

Input
(kW)

Output

(kW)

Temp

Rise

(°C)

Gas Line

Size

(mm. OD)

(27/19-35°C)

Cooling Cap.

(kW)

Options

kW

CoP

2

090

(26.4)

DM

26.1

2.64

87

7, 14,

18, 27

-

-

-

10

-

-

-

-

35.1

28.1

8.3-25

19.05

15

-

-

-

-

52.7

42.2

17-33

19.05

120

(35.1)

DM

34.0

2.64

85

14, 18,

27, 41

-

-

-

-

15

-

-

-

-

52.7

42.2

11-28

19.05

150

(43.9)

DM

40.4

2.64

84

14, 18,

27, 41

-

-

-

-

15

-

-

-

-

52.7

42.2

5.6-22

19.05

1. Electric heaters rated at 415V. See tables 10 through 12 for kW ratings at 380V
2. CoP = Co-efficient of Performance (CoP = Cooling Capacity (kW) / Power Input (kW))

Advertising