TABLE 4: COOLING CAPACITY 7-1/2 TON UNIT - IMPERIAL

Air On

Evap. Coil

Temperature of Air on Condenser Coil 85°F

Temperature of Air on Condenser Coil 95°F

CFM

WB
(°F)

Tot.

Cap.

1

(MBH)

Tot.

Input

2

(kW)

Sensible Capacity (MBH)

1

Return Dry Bulb (°F)

Tot.

Cap.

1

(MBH)

Tot.

Input

2

(kW)

Sensible Capacity (MBH)

1

Return Dry Bulb (°F)

86

83

80

77

74

71

68

86

83

80

77

74

71

68

2250

72

104

8.6

60

54

47

41

34

-

-

98

9.2

57

50

44

37

31

-

-

67

96

8.4

74

68

61

55

48

42

35

90

9.0

71

64

58

51

45

39

32

62

88

8.2

87

81

75

68

62

55

49

80

8.6

80

75

69

63

56

50

43

57

84

8.2

84

83

77

71

64

58

51

78

8.6

78

77

71

64

58

51

45

2625

72

107

8.7

66

59

51

43

36

-

-

101

9.3

63

55

48

40

32

-

-

67

99

8.5

81

73

66

58

51

43

35

92

9.1

78

71

63

55

48

40

33

62

90

8.3

90

87

80

73

65

58

50

83

8.7

83

80

75

68

60

52

45

57

87

8.2

87

86

83

75

68

60

53

81

8.7

81

80

77

69

62

54

46

3000

72

110

8.8

72

63

55

46

37

-

-

104

9.4

69

60

51

43

34

-

-

67

102

8.6

88

79

71

62

53

44

36

95

9.2

86

77

68

59

51

42

33

62

93

8.3

93

93

86

77

69

60

51

86

8.8

86

86

81

72

64

55

46

57

89

8.3

89

89

89

80

71

63

54

83

8.8

83

83

83

74

66

57

48

3375

72

112

8.8

77

68

58

48

38

-

-

106

9.4

74

64

54

44

34

-

-

67

104

8.6

94

84

74

64

54

44

35

97

9.2

92

82

72

62

52

42

32

62

95

8.4

95

95

91

81

71

61

51

87

8.9

87

87

85

75

65

55

45

57

91

8.3

91

91

91

81

71

61

51

84

8.9

84

84

84

74

64

55

45

3750

72

115

8.9

83

72

61

49

38

-

-

108

9.5

79

68

57

46

34

-

-

67

106

8.7

101

89

78

67

56

45

33

99

9.3

97

86

75

64

53

42

30

62

97

8.4

97

97

95

84

73

62

51

88

8.9

88

88

88

77

66

55

44

57

92

8.4

92

92

92

81

70

59

48

86

8.9

86

86

86

75

63

52

41

Temperature of Air on Condenser Coil 105°F

Temperature of Air on Condenser Coil 115°F

2250

72

91

9.8

54

48

41

35

28

-

-

84

10.4

51

45

39

32

26

-

-

67

81

9.5

67

61

54

48

42

35

29

73

10.0

64

57

51

45

38

32

25

62

73

9.1

73

71

64

58

51

45

38

66

9.7

66

66

59

53

46

40

34

57

71

9.1

71

71

64

58

52

45

39

65

9.7

65

65

58

52

45

39

33

2625

72

94

9.9

60

52

45

37

30

-

-

87

10.5

57

50

42

35

27

-

-

67

84

9.6

74

67

59

52

44

37

29

76

10.1

71

63

56

48

40

33

25

62

75

9.3

75

74

70

62

55

47

40

68

9.8

68

68

65

57

49

42

34

57

74

9.3

74

73

70

63

55

47

40

67

9.8

67

67

64

56

48

41

33

3000

72

97

10.0

66

57

49

40

31

-

-

89

10.6

63

54

46

37

28

-

-

67

87

9.7

82

73

64

55

47

38

29

78

10.2

78

69

60

52

43

34

25

62

78

9.4

78

78

76

67

58

49

41

70

9.9

70

70

70

61

53

44

35

57

76

9.4

76

76

76

67

58

50

41

69

9.9

69

69

69

60

51

43

34

3375

72

99

10.1

71

61

51

41

31

-

-

91

10.7

68

58

48

38

28

-

-

67

88

9.8

85

78

68

58

48

38

28

80

10.3

79

74

64

54

44

34

24

62

79

9.4

79

79

78

68

58

48

38

71

10.0

71

71

71

61

51

42

32

57

77

9.4

77

77

77

67

57

47

37

70

10.0

70

70

70

60

50

40

30

3750

72

101

10.1

76

65

54

43

32

-

-

93

10.8

73

62

51

40

29

-

-

67

90

9.8

89

82

71

60

49

38

27

81

10.4

81

79

67

56

45

34

23

62

81

9.5

81

81

81

69

58

47

36

73

10.1

73

73

73

62

50

39

28

57

79

9.5

79

79

79

68

56

45

34

72

10.1

72

72

72

60

49

38

27

Temperature of Air on Condenser Coil 125°F

2250

72

77

11.0

49

42

36

30

23

-

-

67

65

10.5

60

54

48

41

35

28

22

62

59

10.2

59

59

54

48

42

35

29

57

58

10.2

58

58

52

46

39

33

26

2625

72

80

11.1

55

47

39

32

24

-

-

67

67

10.6

67

60

52

44

37

29

22

62

60

10.3

60

60

59

52

44

37

29

57

60

10.3

60

60

57

49

42

34

27

3000

72

82

11.2

60

51

43

34

25

-

-

67

69

10.8

69

65

56

48

39

30

21

62

62

10.4

62

62

62

56

47

38

29

57

62

10.5

62

62

62

53

44

36

27

3375

72

84

11.4

65

55

45

35

26

-

-

67

71

10.9

71

70

60

50

40

30

20

62

64

10.5

64

64

64

55

45

35

25

57

63

10.6

63

63

63

53

43

33

23

3750

72

85

11.5

70

59

48

37

26

-

-

67

72

11.0

72

72

63

52

41

30

19

62

65

10.6

65

65

65

54

43

31

20

57

64

10.7

64

64

64

53

42

31

20

1 These capacities are gross ratings. For net

capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.

2 These ratings include condenser fan motors

and the compressor motors but not the supply
air blower motor.