2nd Ave. Honeywell Relay Modules 7800 Series User Manual

Page 13

Advertising
background image

7800 SERIES RELAY MODULES

13

65-0229—1

Table 3. Hold and Fault Message Summary (continued).

Fault Code

System Failure

Recommended Troubleshooting

Fault 27

*Start Switch On*

Start Switch was on during
PREPURGE (RM7838A,
RM7838B only).

1.

Start Switch held on too long.

2.

Check wiring; verify that Start Switch is correctly connected.

3.

Make sure that the Start Switch is functioning properly and that

the switch contacts are free of contaminants.

4.

Reset and sequence the relay module to PREPURGE; set the

Run/Test Switch to Test. Make sure there is no power at
terminal 6 during PREPURGE.

5.

If steps 1 through 3 are correct and the fault persists, replace

the relay module.

Fault 28

*Pilot Flame Fail*

Pilot flame failure.

1.

Check pilot valve wiring and operation. Correct any errors.

2.

Check fuel supply.

3.

Check pilot pressure and repeat pilot turndown test.

4.

Check ignition transformer electrode, flame detector, flame

detector sighting and flame amplifier.

5.

If steps 1 through 4 are correct and the fault persists, replace

the relay module.

Fault 29

*Lockout ILK*

Lockout Interlock fault.

1.

Check wiring; correct any errors.

2.

Inspect the fan; make sure that there is no blockage of the air

intake and that it is supplying air.

3.

Make sure that the Lockout Interlock Switches are working

properly and that all switch contacts are free of contaminants.

4.

Reset and sequence the relay module to PREPURGE (place the

Run/Test Switch in the Test position, if available). Measure the
voltage between terminals 7 and G (ground). Line voltage
should be present.

5.

If steps 1 through 4 are correct and the fault persists, replace

the relay module.

Fault 30

*Running ILK*

Running Interlock fault.

1.

Inspect the Running Interlocks, including the Airflow Switch,

and the connections.

2.

Make sure that the Running Interlocks, including the Airflow

Switch, are functioning properly and that switch contacts are
free of contaminants.

3.

Reset and sequence the relay module to PREPURGE. Set the

Run/Test Switch, if available, to Test. Measure the voltage
between terminal 7 and G (ground). Line voltage should be
present.

4.

If steps 1 through 3 are correct and the fault persists, replace

the relay module.

Fault 31

*Low Fire Sw. Off*

Low Fire Interlock Switch
failure to close during RUN
(RM7838B only).

1.

Check wiring; correct any errors.

2.

Reset and sequence the relay module.

3.

Use either the manual motor position to drive the motor to the

Low Fire position, or use the Run/Test Switch option, if
available. Sequence to Run drive to Low Fire and place in the
Test position. Adjust the Low Fire Switch while in this state to
make sure it is closing properly.

4.

While in Run, drive to Low Fire state, measure the voltage

between terminal 18 and G (ground). Line voltage should be
present. If not, the switch adjustment is incorrect and/or the
switch is defective and needs replacement.

5.

Reset and sequence the relay module. If line voltage was

present between the Low Fire Switch and terminal 18 and the
fault persists, replace the relay module.

(continued)

(continued)

Advertising