2nd Ave. Honeywell Relay Modules 7800 Series User Manual

Page 18

Advertising
background image

18

7800 SERIES RELAY MODULES

65-0229—1

Table 3. Hold and Fault Message Summary (continued).

Fault Code

System Failure

Recommended Troubleshooting

Fault 109

*Call Service*

Negative cycle test failed,
earth ground absent or line
voltage phasing improper.

1.

Make sure a good earth ground connection exists at the

installation site and all earth ground connections are complete
and correct.

2.

Make sure the relay module and all loads operate at the same

line voltage phase.

3.

Reset and sequence the relay module.

4.

If the fault persists, replace the relay module.

Fault 110

*Call Service*

The configuration jumpers
differ from stored values.

1.

Inspect the jumper connections. Make sure they match the

original selection and clipped jumpers are completely
removed.

2.

Reset and sequence the relay module.

3.

If the fault persists, replace the relay module.

4.

Configuration jumpers must be selected prior to 200 hours of

operation. If configuration jumpers are changed after 200
hours of operation, lockout 110 occurs. Relay module

cannot

be reset and

must be replaced.

Fault 111

*Call Service*

Relay Module configuration
jumper test failure.

1.

Inspect the jumper connections. Make sure they match the

original selection and clipped jumpers are completely
removed.

2.

Reset and sequence the relay module.

3.

If the fault persists, replace the relay module.

Fault 112 - 126
*Call Service*

Relay Module self-test
failure.

1.

Reset and sequence the relay module.

2.

If the fault persists, replace the relay module.

Fault 127

*Call Service*

Safety relay feedback circuit
was in an improper state.

1.

Reset and sequence the relay module.

2.

If the fault persists, replace the relay module.

Advertising