7800 SERIES RELAY MODULES

17

65-0229—1

Table 3. Hold and Fault Message Summary (continued).

(continued)

Fault Code

System Failure

Recommended Troubleshooting

Fault 68

*Preignition ILK*

Preignition Interlock fault.

1.

Check wiring; correct any errors.

2.

Inspect the Preignition Interlock switches and make sure

they work properly.

3.

Check fuel valve operation. Valve must close within five

seconds.

4.

Reset and sequence the relay module.

5.

During STANDBY or PREPURGE, measure the voltage

between terminal 17 and G (ground). Supply voltage should
be present. If not, the Preignition Interlock switches are
defective and need replacing.

6.

If the fault persists, replace the relay module.

Fault 69 - 70

*Call Service*

Unused faults.

Fault 71

*Dynamic LFS*

Low Fire Switch closed, High
Fire Switch must be open
(EC/RM7850 only).

1.

Check firing rate position switches (usually in Modutrol®

Motor) for proper operation.

2.

Check wiring, correct any errors.

3.

Reset and sequence the relay module.

4.

If the fault persists, replace the relay module.

Fault 71

*Limits Complete*

Limit input (terminal 7) is off
when it should be on (RM7888
only).

1.

Check limits to make sure they are satisfied after resetting.

2.

Check electrical connections to terminal 7 of wiring

subbase.

3.

Reset relay module.

4.

If the fault persists, replace the relay module.

Fault 72

*Dynamic HFS*

High Fire Switch closed; Low
Fire Switch must be open
(EC/RM7850 only).

1.

Check firing rate position switches (usually in Modutrol®

Motor) for proper operation.

2.

Check wiring, correct any errors.

3.

Reset and sequence the relay module.

4.

If the fault persists, replace the relay module.

Fault 72

*Spec.Func.2*

Special Function 2 Input
(terminal 17) is off when it should
be on.

1.

Check operation of Special Function 2 of PLC.

2.

Check electrical connection to terminal 17 of wiring

subbase and confirm presence of supply power when
Special
Function 2 is activated.

3.

Reset relay module.

4.

If the fault persists, replace the relay module.

Fault 73

*Spec.Func.3*

Special Function 3 Input
(terminal 19) is off when it should
be on.

1.

Check operation of Special Function 3 of PLC.

2.

Check electrical connection to terminal 19 of wiring

subbase and confirm presence of supply power when
Special
Function 3 is activated.

3.

Reset relay module.

4.

If the fault persists, replace the relay module.

Fault 75

*Flame Proven

Feedback*

Flame Indication Feedback
(terminal 21) either on when it
should be off or off when it
should be on.

1.

Remove wire to terminal 21 and reset relay module.

2.

If the fault persists, replace relay module.

3.

Reconnect wire to terminal 21. If the fault returns, verify

wiring.

Fault 76 - 93

*Accessory Fault*

Fault 94 - 104
*Call Service*

Fault 105

*Call Service*

Relay Module self-test failure.

1.

Reset and sequence the relay module.

2.

If the fault reappears, remove power from the relay module

Fault 106

*Call Service*

Relay Module self-test failure.

and reapply the power; reset and sequence the relay
module.

3.

If the fault persists, replace the relay module.

Fault 107

*Call Service*

Relay Module flame signal
crosscheck failure.