Warning – 2nd Ave. Honeywell Relay Modules 7800 Series User Manual

Page 15

Advertising
background image

7800 SERIES RELAY MODULES

15

65-0229—1

Table 3. Hold and Fault Message Summary (continued).

Fault Code

System Failure

Recommended Troubleshooting

Fault 45

*Low Fire Sw. Off*

Low Fire Interlock switch failure
to close or stay closed.

1.

Check wiring; correct any errors.

2.

Reset and sequence the relay module.

3.

Use either the manual motor position to drive the motor to

the Low Fire position, or use the Run/Test Switch option, if
available. Sequence to Run, drive to Low Fire and place in
the Test position. Adjust the Low Fire Switch while in this
state to make sure it is closing properly.

4.

While in Run, drive to Low Fire state, measure the voltage

between terminal 18 and G (ground). Line voltage should
be present. If not, the switch adjustment is incorrect
and/or the switch is defective and needs replacement.

5.

If steps 1 through 4 are correct and the fault still persists,

replace the relay module.

Fault 46

*Flame Amp Type*

This fault indicates:
a.

The Flame Failure Response
Time (FFRT) or TYPE input
from the amplifier changed
while the device was
powered; or

b.

A standard amplifier was
used in a pilot valve
application; or

c.

A three-second FFRT

Amplifier was used with the
relight option on the
RM7890 Relay Module.

1.

Remove power to the device.

2.

Reseat the flame amplifier and reset and sequence the relay

module.

3.

For EC/RM7890 only; make sure that Jumper JR2 is

completely clipped if a three-second FFRT amplifier is
being used. If Jumper JR2 is intact (relight option is
selected), use 0.8 second FFRT amplifier.

4.

For RM7838B only; make sure that a Shutter Check Flame

Amplifier is being used with the Pilot Valve Hold option
selected.

Fault 47

*Jumpers Changed*

The configuration jumpers differ
from the sample taken at startup.

1.

Inspect the jumper connections. Make sure that clipped

jumpers are completely removed.

2.

Reset and sequence the relay module.

3.

If fault persists, replace the relay module.

Fault 48

*Delayed MV On*

V2S valve terminal, used as a
delayed main valve, was on when
it should be off.

WARNING

Explosion Hazard.
Can cause explosion, serious injury or death.
1.

Remove system power, turn off fuel supply.

2.

Check wiring; correct any errors.

3.

Inspect the V2S Fuel Valve and its connections.

Make sure the switch is working correctly and is not
jumpered or welded.

4.

Reset and sequence the relay module.

5.

If fault persists, replace the relay module.

Fault 49

*Man-Open Sw. On.*

The manual open switch was on
when it should be off.

WARNING

Explosion Hazard.
Can cause explosion, serious injury or death.
1.

Remove system power, turn off fuel supply.

2.

Check wiring; correct any errors.

3.

Inspect the Manual-Open Switch and its

connections. Make sure the switch is working
correctly and is not jumpered or welded.

4.

Reset and sequence the relay module.

5.

If fault persists, replace the relay module.

Fault 50

*Jumpers Wrong*

The sequence logic detected a
combination of jumpers that is
illegal for the sequence eg, if it is
correct to clip Jumper JR1 or
Jumper JR2, but not both, this
fault would be used when both
are clipped (RM7888 only).

1.

Inspect the jumpers and refer to the installation instructions

for compatible jumper configurations.

2.

Make sure that clipped jumpers are completely removed.

3.

Reset and sequence the relay module.

4.

If fault persists, replace the relay module.

(continued)

Advertising